Siemens TL.. Bedienerhandbuch Seite 18

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 66
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 17
16
Operating Instructions
Operating the SB Encased Systems Breaker
Manually Charging the Stored Energy Mechanism
The stored energy mechanism may be charged with the SB
breaker open or closed. If the stored energy mechanism is
charged with the breaker open, sufficient energy is stored to
close and then open the breaker without recharging. If the
stored energy mechanism is charged with the breaker closed,
the operating sequence of open-close-open may be executed
without recharging. To manually charge the stored energy
mechanism, pull the charging handle.
Five or six full strokes, or several partial strokes are required to
fully charge the stored energy mechanism. When the stored
energy mechanism is fully charged, Spring Charged/Spring
Discharged indicator points to Spring Charged. The charging
handle returns to the stowed position when released. While
manually charging the breaker with the charging handle,
do
not
depress the Push-to-Close or Push-to-Open push buttons.
If an optional electric motor operator is employed, the electric
operator automatically recharges the stored energy mecha-
nism when the breaker is closed. If the electric operator is dis-
abled, the stored energy mechanism may be charged
manually.
CAUTION
!
Do not exert further downward pressure
when springs are charged or handle is
against bottom stop as shown in the
illustration below. Potential damage to
housing may occur.
To manually charge the stored energy mechanism, pull the charging handle downward five or six strokes until indicator points to
“Spring Charged.