Seitenansicht 95
Diagnostics over Industrial Ethernet
6.2 Web Based Management (WBM)
6.2.4.19 The "Switch Port Diagnostics" WBM Menu
Switch Port Diagnostics
With this dialog, each individual Ethernet port can run independent fault diagnostics on the
cable. This test can be made without the cable being connected if a cable tester is
connected and a loopback module is installed at the other end. This allows short-circuits and
cable breaks to be localized to within a few meters.
Notice
Please note that this test is permitted only when no data connection is established on the
port to be tested.
Figure 6-24 "Switch Port Diagnostics" Dialog
Port Text Box
The port to be tested is specified here.
Run Test Button
This button activates the test.
Pair Information Box
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
6-28 Commissioning Manual, 1,