26 / 32
Siemens RDU340… Basic Documentation CE1P3078en
Building Technologies Engineering 2014-09-05
6 Engineering
6.1 Connection terminals
G X1M
G0
Y21
Y10 G0
SELV
X2
L
G, G0 Operating voltage controller AC 24 V
L Operating voltage for electrical heater AC
230 V
Y21 Control output for electrical heater
Y10 Control output for DC 0…10 V actuator
X1, X2 Multifunctional input for temperature
sensor (e.g. QAH11.1) or switch
M Measuring neutral for sensor and switch
6.2 Connection diagrams
Application:
Single duct
N1 Room temperature controller RDU340...
Y1 DC 0-10V actuator for heating or cooling
S1 Operating mode switch-over contact
(e.g. key card)
B2 Heat/cool changeover sensor
10A
G
Application:
Single duct with
electrical heater
N1 Room temperature controller RDU340...
Y1 DC 0-10V actuator for heating or cooling
E1 Electrical heater
S1 Operating mode switch-over contact
(e.g. key card)
B2 Heat/cool changeover sensor
Kommentare zu diesen Handbüchern