Interrupts/diagnostics alarms
5.1 Status and error displays
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
27
Meaning of the LED displays
The following tables explain the meaning of the status and error displays. Remedial
measures for diagnostic alarms can be found in section Diagnostic alarms.
Table 5- 1 Status and error displays RUN and ERROR
Off
Off
Voltage missing or too low at backplane bus.
• Switch on the CPU and/or the system power
supply modules.
• Verify that the U connectors are inserted.
• Check to see if too many modules are insert-
ed.
The module starts and flashes until the valid
parameter assignment is set.
---
Module is configured.
Indicates module errors (at least one error at
one channel, e.g., wire break).
Evaluate the diagnostics data and eliminate the
error (e.g., wire break).
Hardware defective. Replace the module.
Table 5- 2 PWR status display
Supply voltage L+ to module too low or missing Check supply voltage L+.
Supply voltage L+ is present and OK. ---