Commissioning and Diagnostics
6-39
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Removal/Insertion Interrupt with S7/M7-DP Master or DPV1 Master
If you use the ET 200M with module change during operation on an S7/M7-DP
master or a DPV1 master, the system behaves as follows:
When a module is removed, the IM 153-x reports a module removal interrupt on
the DP master that executes OB 83. You program the desired response to the
module removal event in OB 83.
In the case of I/O access, OB 122 (I/O access error) is called in the DP master.
If you insert a module that corresponds to the configuration, the IM 153-x
reports a module insertion interrupt to the DP master (OB 83 call with
diagnostics buffer entry) and assigns parameters to the module in keeping with
the stored configuration.
If you insert a module in an unconfigured slot, the IM 153-x doesnt report a
module insertion interrupt.
If you insert a different module than configured:
the IM 153-x reports a module insertion interrupt to the DP master (OB 83
call with diagnostics buffer entry); but it ignores this unconfigured module.
The module diagnosis is stopped, and you can read out the slot in which the
wrong module is inserted (see Section 6.4.5).
The SF LED shows the error.
Note: Inserting or removing a DM 370 dummy module does not trigger an insertion
or removal interrupt.
!
Warning
Problems during removal and insertion are tolerated for up to 1 second.
This means that the output values will not change within the tolerance time in the
event of such a problem occurring.