Inputs
Sensor input: Isolated HRR® sensor
Range: -500 mV to +1000 mV
Sensing accuracy: ± .1% per year
Resolution: 1 mV
Digital Inputs: Contact Closure
(Totalizer & ChemFeed trigger)
Sample Flow Switch
(Blowdown & ChemFeed
enable)
Outputs
Analog outputs: (4) Isolated fully rangeable
4-20mA up to 750 ohms with record and
control capabilities
Three programmable relays for chemical
control, alarm, sensor wash, or triggered
timer function.
120/240 VAC, 50/60 Hz
Two 5 Amp, one 1 Amp
Resolution ± .5%
Strantrol, HRR and High Resolution Redox are trademarks of Siemens, its subsidiaries or affiliates.
UL is a registrered trademark of Underwriters Laboratories, Inc.
The information provided in this brochure contains merely general descriptions or characteristics of
performance which in actual case of use do not always apply as described or which may change as a
result of further development of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the terms of the contract.
Siemens
Water Technologies
595 Industrial Drive
Bradley, IL 60915, USA
800.809.0971 phone
www.usfilter.com
Literature No. ST-887-DS-0806
Subject to change without notice.
©2006 Siemens Water Technologies Corp.
User Interface
Display: 16 character backlit LCD display
shows real time sensor readings, alarms,
programming values and menus.
Keypad: 7 pressure sensitive keys for setting
calibration, control setpoint, alarms, 4-
20mA, triggered timer, totalizer, and sensor
clean values. UP, DOWN, PREV, and ENTER
keys for scrolling through menu and
changing settings. CAL button for single
point calibration. SETPOINT for changing the
control value. MENU for more detailed
configuration.
Options
Automatic sensor washing: Recommended
for high TDS applications such as recirculated
cooling water. On-line sensor washing is
available by requesting the optional
diaphragm pump and tank package (part no.
7149002).
Sample flow switch: The optional sample
flow switch assures that when the sample
stream is interrupted for any reason, the
feed of chemicals is halted. This is a valuable
safety device as well as a way to prevent
overfeeding of chemical due to a trapped
“dead” sample.
Ratings
ETL approved to UL® Standard 508A
CE approved for heavy industrial use
Voltage: 120/250 VAC, 50/60 Hz
Total Current: 12 amps
Enclosure
Rating: NEMA 4X (IP 66)
Dimensions: (H x W x D)
7.1” x 7.2” x 4.4” in
(180 x 182 x 111 mm)
Weight: 2.1 pounds (0.95 kg)
Material: UL® Listed
Polycarbonate
Sample Flowcell
Design ensures sensor remains wetted at all
times. Flowcell comes complete with fittings,
including two isolation valves and a sample
tap. Flowcell cover is clear permitting on-line
inspection of sensor tip.
Material: Schedule 80 PVC
Pressure: Tested to 100 psig
(6.8 bar)
Temperature: 120
0
F (48.8
0
C) (Max)
Cover: Clear Polycarbonate
4 7/8”
4 3/8”
1/2”
2 1/8”
9”
7”
1”
5/8”
7 1/8”
21”
19”
9”
12 1/4”
Strantrol® 887 HRR Controller