Analog Modules
5-125
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 431; AI 8 RTD 16 Bit
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 650 g
Data for Specific Module
Number of inputs
For resistance-type sensor
8
4
Length of cable
Shielded Max. 200 m
Voltages, Currents, Potentials
Constant current for
resistance-type sensor
Max. 1 mA
Isolation
Between channels and
backplane bus
Yes
Permitted potential difference
Between M
ANA
and
M
internal
(U
ISO
)
120 VAC
Insulation tested with 1500 VAC
Current consumption
From the backplane bus Max. 650 mA
Power dissipation of the
module
Typ. 3.3 W
Analog Value Generation
Measuring principle Integrative
Integration/conversion time/
resolution (per channel)
Parameterizable
(Does not go into the
response time)
Yes
Basic conversion time in
ms
22/25
Additional conversion time
for measuring resistance,
in ms
Max. 200
Resolution including sign 16/16 bit
Noise suppression
for interference frequency
f1 in Hz
60/50
Smoothing of the measured
values
Parameters can be
assigned in 4 stages
Basic response time of module
(all channels enabled)
22/25 ms
Suppression of interference, Limits of Error
Noise suppression for f = n (f1 "1%),
(f1 = interference frequency) n = 1, 2, etc.
Common-mode
interference (U
CM
< 120V)
Series-mode interference
(peak value of interference
< rated value of the input
range)
> 100 dB
> 50 dB
Crosstalk between the inputs
> 70 dB
Operational limit (over entire temperature range, referred
to 0 to 60 C input range)
RTD input " 1.0 °C
Basic error (operational limit at 25 °C, referred to input
range)
RTD input " 0.5 °C
Temperature error (with
reference to the input range)
" 0.007%/K
Linearity error (with reference
to the input range)
" 0.2 °C
Repeat accuracy (in the steady
state at 25
°C, referred to the
input range)
" 0.2 °C
Status, Interrupts, Diagnostics
Interrupts
Hardware interrupt when
limit has been exceeded
Parameters can be
assigned
Diagnostic Interrupt Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
Group error display
For internal fault
For external fault
Red LED (INTF)
Red LED (EXTF)
Diagnostic information can
be displayed
Possible
Data for Selecting a Sensor
Input range (rated values) input
resistance
Resistance thermometer Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000
Maximum input voltage for
voltage input (destruction
limit)
35 V continuous;
75 V for max. 1 s
(duty factor 1:20)
Connection of the sensor
For measuring resistance
With three-conductor
terminal
Possible
With four-conductor
terminal
Possible
Characteristic linearization
For resistance
thermometer
Pt 100,0,00385 to DIN
IEC 751
Ni 100, 0,00618 to DIN
43760
Unit for temperature
measurement
Degrees Celsius;
degrees Fahrenheit