Diagnostic data of signal modules
B.5 Diagnostic data of the analog input modules as of byte 2
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
439
Bytes 8 and 23 of the SM 431; AI 8 x RTD x 16 bit
Data record 1 contains the channel-specific diagnostic data, starting at bytes 8 to 23. The
following table shows the assignment of the even diagnostic bytes (bytes 8, 10, to 22) for a
channel of the module.
Table B- 23 Even diagnostic byte for a channel of the SM 431; AI 8 x RTD x 16 bit
Byte Bit Meaning
7 Overflow
6 Underflow
5 0
4 Wire break
3 0
2 0
1 0
Byte 8-23
even
0 Configuring/parameter assignment error
The following table shows the assignment of the odd diagnostic bytes (bytes 9, 11, to 23) for
a channel of the module.
Table B- 24 Odd diagnostic byte for a channel of the SM 431; AI 8 x RTD x 16 bit
Byte Bit Meaning
7 User calibration does not correspond to the parameter assignment
6 Open conductor in the current source
5 0
4 Underrange or overrange
3 Run time calibration error
2 Open conductor in - direction
1 Open conductor in + direction
Byte 8-23
odd
0 User connection not wired
Bytes 2 and 3 of the SM 431; AI 8 x 16 bit
Table B- 25 Bytes 2 and 3 of the diagnostic data of the SM 431; AI 8 x 16 bit
Byte Bit Meaning
7 0
6 0
5 0
4 0
3 0
2 Operating mode 0: RUN; 1: STOP
1 0
Byte 2
0 Thermocouple connection error