Level Measurement
Continuous level measurement - Ultrasonic controllers
SITRANS LU AO
5/166
Siemens FI 01 · 2011
5
Overview
The SITRANS LU AO Analog Output Module provides remote an-
alog output for the measurement points of the SITRANS LU10
level monitor.
Benefits
Analog outputs can be up to 1500 m (5000 ft) from the
SITRANS LU10
Analog outputs can be per transducer and/or average of 2 or
more
Application
The operation of the SITRANS LU AO is programmed via the
SITRANS LU10. The only on-board settings are for bank selec-
tion and output testing.
The SITRANS LU AO can provide up to 10 analog outputs (each
sharing a common negative bus which is electrically isolated
from ground).
Technical specifications
C) Subject to export regulations AL: N, ECCN: EAR99
Mode of operation Output module
Input
Communications Data from SITRANS LU10
• Transmission rate
4800 bits/s
• Voltage
± 20 mA bipolar current loop
• Polarization
Non-polarized
• Max. load
1 receiving unit
Output
Analog outputs 10 analog outputs, programmable
from SITRANS LU10
0 or 4 ... 20 mA, isolated
± 20 mA bipolar current loop
Input and transmission
• Max. load
750
• Resolution
0.1 %
Rated operating conditions
Ambient conditions
• Ambient temperature for enclosure -20 ... +50 °C (-5 ... +122 °F)
• Location
Indoor/outdoor
• Installation category
II
• Pollution degree
4
Design
Weight 2 kg (4.4 lbs)
Material (enclosure) Polycarbonate
Degree of protection
Type 4X/NEMA 4X/IP65
• Cable connection 2 copper conductors, twisted,
with foil shield/drain wire, 300 V
0.5 ... 0.75 mm² (22 ... 18 AWG)
• Electrical connection and relay
connection
Copper conductor according to
local requirements,
rated 250 V 5 A
Power supply
100/115/200/230 V AC ± 15 %,
50/60 Hz, 15 VA
Displays and controls
1 LED for display of voltage/com-
munications state
Certificates and approvals
CE, FM, CSA
US/C
, C-TICK
Selection and Ordering data
Order No.
SITRANS LU AO
Provides remote analog output for the measure-
ment points of the SITRANS LU10 level monitor.
Approvals: CSA
US/C
, FM, CE, C-TICK
C)
7ML5810-1A
Operating Instructions
English
C)
7ML1998-5CE01
German
Note: Instruction manuals should be ordered as a
separate line item on the order.
C)
7ML1998-5CE31
This device is shipped with the Siemens Milltronics
manual CD containing the complete Quick Start and
instruction manual library.