How to OrderSB Encased Systems Breakers
1
Example
Catalog
Description Number Example Catalog Number Explanation
1. Frames SBS2016DV This catalog number represents a standard interrupting rated
Select basic breaker frame catalog number from Encased Systems Breaker “SBS,” 2000 ampere frame size “20”;
Table A. 1600 max ampere rating “16”; drawout mounted with vertical
bus orientation “DV”
2. Drawout Mechanisms SBS20DFV This catalog number represents the stationary drawout
Select the proper stationary drawout element (cradle) element (cradle) for a 2000 ampere frame size, standard
for use with breaker frame selected in Step 1. Station- interrupting rating, drawout mounted Encased Systems
ary drawout mechanism is not required if fixed mounted Breaker with vertical bus orientation.
breaker was selected in Step 1. Select from Table B.
3. Pressure Wire/Bus Connectors A drawout mounted breaker was selected in Step 1, there-
For fixed mounted
breakers only, select proper terminals fore, terminals or bus “T” connectors are not required.
for cable connection; or bus connectors for rear bus bar
connection. Not required if drawout mounted breaker
was selected in Step 1. Select from Table C.
4. Trip Units SB16TP01G This catalog number represents a trip unit for a 1600 frame
Select SB-EC Trip Unit or standard Type “TL” Trip ampere rating Encased Systems Breaker with long and time
Unit with proper function package from Table D and delay, short time pickup and time time pickup delay, ground
E or Table L respectively. Trip unit is not required for fault pickup and time delay and standard metering and
Non-Automatic Switches. alarm functions.
5. A premium type SB-EC Trip Unit requires the listed SBEPS AN SB-EC Trip Unit was selected, therefore an External Power
accessories shown. Refer to TABLES F, G and H. Supply is required for communications and metering functions.
One required per SB-EC Trip Unit.
The standard Type “TL” Trip Unit does not use SBPTM480 One PT Module per SB-EC Trip Unit is required for metering
these accessories functions. Select according to system voltage. This catalog
number represents a 480V system voltage Potential Transformer.
SBECDAK One wiring kit per SB-EC Trip Unit is required. Select according
to Breaker Frame Size and mounting configuration. This wiring
kit is for a 2000 A Frame Size, Drawout mounting.
6. Rating Plugs 16SB1200 This catalog number represents a 1200 ampere continuous
Select the proper rating plug for the breaker ampere current rating plug for a 1600 frame ampere rating breaker.
rating from Table M. Rating plug is not required for
Non-Automatic Switches.
7. Electrical Operators SBEO120 This catalog number represents a 120 volt electrical operator
Select proper electrical operator, if required, for breaker for a 2000 ampere frame size Encased Systems Breaker. A
frame size and control voltage from Table N. Shunt Trip or Undervoltage Release should be ordered and
priced separately.
8. Internal Accessories SBST120 120 VAC Control Power Shunt Trip for remote open
List the required internal accessories catalog numbers
from pages 8-12. List each catalog number and SBUV480 480 Volt AC, undervoltage release
price separately.
SBAS6 3 NO (normally open), 3 NC (normally closed) auxiliary switches
9. External Accessories SBWIN Windows based function display and configuration software
List the required external accessories catalog numbers for PC
rom pages 9-12. List each catalog number and price
separately. KISB Kirk Key Interlock on breaker
SBPLD Padlocking Device on drawout
NB16SB Neutral Sensor for 1600 frame ampere rating breaker
10. Secondary Contact Blocks SBSDLT Secondary disconnects for this drawout breaker are required
Proper secondary contact blocks for external control for certain trip unit functions, internal and external accessories
wiring must be provided on drawout mounted breakers. SBSDRT as shown in Table P. This example requires the following:
Select the proper catalog numbers based on the breaker
trip unit functions and internal accessories that were BSBDRB
selected in Steps 5, 6, 7 and 8 above. Select from
Table P. Note: Secondary contact blocks are not
required on fixed mounted breakers, but control
terminal blocks and mounting brackets should be
ordered for secondary control wiring on fixed mount
breakers. Refer to page 9, Table P for additional
information.
1
Refer to SB Encased System Breakers Selection Guide for detailed selection information for SB breakers and related accessories.
2
Refer to Discount Schedule T unless specified.
Sliding
Function/ Contact Secondary
Accessory Position Disconnect
Electrical Operator LT SBSDLT
Undervoltage Release,
Neutral CT, Shunt Trip
Auxiliary Switches RB SBSDRB
(3A & 3B)
SB-EC Trip Unit RT & LB SBSDRT
SBSDLB