15
Technical features
SPC5320.320-L1
SPC5330.320-L1
INTRUSION
Programmable areas
16
Number of on-board zones
8
Max. number of hardwired zones
128
Supervised input
No EOL / Single EOL / Dual EOL / Tri EOL (Antimask PIR) / Inertia Sensors
EOL resistor
4K7 (default), other resistor combinations configurable
Number of on-board outputs
6
Max. number of outputs
128
Max. number of user codes
256
Event memory
10,000 intrusion events
Calendar based time channels
32 (53-week calendar)
Cause & Effects
256 triggers / 128 mapping gates
Language
Multi-language support (de, en, es, fr, it, nl, sv, vls, plus 1 imported language file)
Voice assistance
Supported
Financial functions
Supported
FIELD BUS
Bus connections
X-BUS (2 spurs or 1 loop)
Number of field devices
1)
48 (16 Keypads, 16 Door-expanders, 16 Input/Output expanders)
CONNECTIVITY
Web Server
HTTPS (embedded)
Pluggable Communication Interfaces
PSTN or GSM/GPRS modem (system supports 2 optional modems simultaneously)
Standard Communication Protocol
SIA, Contact ID, SMS messaging
Fast Programmer Support
Yes
Firmware Upgrade
Local and remote upgrade for controller, peripherals and GSM/PSTN module
SMS event notification / Panel control
With GSM option
Local and Remote configuration
(SPC Pro support)
Via RS232, USB, PSTN, GSM,
IP over Ethernet
Via RS232, USB, PSTN, GSM,
IP over Ethernet
Automated Remote Maintenance
(SPC RM support)
Via PSTN, GSM,
IP over Ethernet
Via PSTN, GSM,
IP over Ethernet
Automated Site Administration
(SPC Safe support)
Via IP over Ethernet
Via IP over Ethernet
IP Alarm and Event transmission
(SPC Com XT support)
IP over Ethernet / GPRS
IP over Ethernet / GPRS
ACCESS
Event memory
10’000 access events
Max. number of doors (entry / entry-exit)
16 / 16
Max. number of door groups
16
Supported card technologies
EM4102 / SiPass, Wiegand 26-bits, HID Corporate 1000
Pass-back prevention (soft / hard)
Yes
ALARM VERIFICATION
Number of verification zones
8 (combined audio and/or video devices)
Audio
Max. 8 audio devices (SPCV32x audio expander, SPCK623 keypad),
up to 60 sec. pre / 60 sec. post audio recording
Video
Max. 4 IP cameras (Siemens CCIC1410 / CFMC1315, Generic),
up to 16 pre / 16 post event images (by JPEG resolution 320 x 240, max. 1 frame / sec.)
WIRELESS
Max. number of wireless zones
2)
120
Max. number of wireless remote controls
256
Max. number of Intrunet wireless detectors
received by any wireless receiver
(recommended)
20
1)
More I/O expanders can be addressed instead of a keypad or door expander, but number of programmable inputs / outputs cannot exceed specified system limits.
2)
A wireless zone takes away a wired zone / optional RF receivers required.