Point Mapping Tables
The following table shows the points available for mapping in the Siemens
Model 4300 Power Meter:
4300 Power
Meter
Table 5: Siemens 4300 Power Meter
NPT
1
NPA
2
Unit Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
%
kW
kW
kW
kWh
Volt
Volt
Amps
MW
MW
MW
MWh
Power Factor (positive value indicates lagging)
Kilowatts (power)
Kilowatt Demand
Maximum Kilowatt Demand
Kilowatt Hours (net)
Voltage L-L Average
Voltage L-N Average
Average Current
Megawatts (power)
Megawatt Demand
Maximum Megawatt Demand
Megawatt Hours (net)
BO
BO
1
2
Clear kW Hours
3
0-N/A, 1-res
Reset Max. kW Demand
3
0-N/A, 1-res
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
Volt
Volt
Volt
Volt
Volt
Volt
Amps
Amps
Amps
A-N Phase Voltage
B-N Phase Voltage
C-N Phase Voltage
A-B Line Voltage
B-C Line Voltage
C-A Line Voltage
Phase A Current
Phase B Current
Phase C Current
1 Network Point Type
2 Network Point Address
3 Do not map these points to Companion Binary Output (BO) points. If you map these
points to Metasys system BO points, make sure the Auto Restore option in the BO
object’s Definition or Focus window is disabled.
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine
the NPT (Network
Point Type) and
NPA (Network Point
Address). For
example, the
hardware reference
for the Kilowatt
Demand point is
AI3.
Metasys Integrator—Metasys Integrator Siemens Application 13