Siemens TCP/IP Ethernet Driver Help
Link Type TSAP Value (hex)
PG 4B57 ('KW')
Configured A remote (client) TSAP configured in Micro/WIN's Ethernet wizard.
If Micro/WIN remote TSAP=xx.yy*, set local TSAP to xxyy.
Remote TSAP
Link Type TSAP Value (hex)
PG 4B57 ('KW')
Configured A local (server) TSAP configured in Micro/WIN's Ethernet wizard.
If Micro/WIN remote TSAP=xx.yy*, set local TSAP to xxyy.
*TSAP as displayed in Micro/WIN's Ethernet Wizard. When accessed from V memory, the value may be in decimal
form. For example, if TSAP is 10.00, the V memory value will be 1000 hex or 4096 decimal. The values entered
for Local TSAP must be in hexadecimal notation; in this example, the value 1000 would be entered.
General Rule From the Perspective of the OPC Server
Local TSAP==Micro/WIN remote TSAP
Remote TSAP==Micro/WIN local TSAP
For information on using the CP243-1 module, refer to How to Configure S7-200 Connections in
Micro/WIN.
S7-300/400/1200/1500 Communications Parameters
This setting does not apply to models utilizing the NetLink adapter (NetLink: S7-300 and NetLink: S7-400).
Link Settings
The communication link refers to the connection between the Siemens TCP/IP Ethernet Driver and the CP.
Type
The type of link chosen determines the number of simultaneous requests allowed. The greater the number of
simultaneous requests, the greater the data throughput. Each device connection is allowed one outstanding
request. To achieve multiple simultaneous requests, multiple connections must be configured. This is achieved
by defining the device multiple times in the OPC server (identical device properties). The devices can be defined
within the same channel or under separate channels. For more information, refer to Optimizing Siemens
TCP/IP Ethernet Communication.
Channel.Device=1 CP connection
There are three types of links: PC (applications), OP (operator panel), and PG (programming device). OP and PG
are usually reserved but can be used if all PC connections are taken.
Type S7-300 CPU 314, 315 S7-400 CPU 412, 413 S7-400 CPU 414 S7-400 CPU 416
PC 2 14 30 62
OP 1 1 1 1
PG 1 1 1 1
Default Number Simultaneous Requests
Example:
Given an S7-400 CPU 412, 14 simultaneous requests can be achieved by defining 14 identical devices in the OPC
server with all configured for Link Type PC. In addition to the PC connections, two more devices can be configured
for Link Type OP and PG. This provides 16 connections overall.
Caution: Connection resources are shared amongst applications communicating with the CP. If another
application such as STEP 7 is configured to use Industrial Ethernet over TCP/IP, at least one PG/PC connection
must be left open for that application to use.
Note:
For information on increasing the number of PG, OP and PC type connections, refer to How to Configure S7-
300/400 Connections in STEP 7.