3 / 8
Siemens Electromotoric actuators CE1N4540en
Building Technologies 05.11.2009
• The valve opens / closes in proportion to the control signal at Y or R.
• At DC 0 V or 0 Ω the valve is closed (A AB).
• When power supply is removed, the actuator maintains its current position.
Connector S1 (under the cover, on the printed circuit board) can be repositioned to
change the flow characteristic of valves from "equal percentage" to "linear"; in all cases
the flow characteristic relates to the through-port of the valve.
S1 connected to A and C:
equal-percentage flow characteristic
S1 connected to B and C:
linear flow characteristic
(factory setting)
4573Z02
R - M
A C B
S1
Ω
C B
Volumetric flow rate
l
i
n
l
o
g
4540D01
V
100
V
0
0 V
0
10 V
1000 Ω
Positioning signal
Relationship between the DC 0…10 V or
0…1000 Ω positioning signal and the
volumetric flow rate
Control signals:
Y = DC 0...10 V
R = 0...1000 Ω; cut through R − M bridge
Flow characteristic
log = Equal-percentage valve characteristic
(factory setting)
lin = Linear valve characteristic
Flow range
V
100
= Volumetric flow 100%
V
0
= Volumetric flow 0 %
Positioning signal Y
DC 0…10 V
DC 0…10 V
Signal R
0…1000 Ω
1)
0…1000 Ω
1)
Position / stroke
The Y positioning signal
is valued.
The R signal is valued. Signal addition Y and R
Position feedback U
DC 0…10 V DC 0…10 V DC 0…10 V
1)
Use with 0…1000 Ω signal indicator, e.g. frost protection. For details see connection diagram.
• Electromotoric actuator, maintenance-free
• Reversible synchronous motor
• Antilocking gear train
• Load-dependent switch-off in stroke limit positions
Engineering notes
The actuators must be electrically connected in accordance with local regulations and
the connection diagrams.
Safety regulations and restrictions designed to ensure the safety of people and
property must be observed at all times.
Admissible temperatures refer to "Technical data" (page 5).
If an auxiliary switch is required, its switching point should be indicated on the plant
schematic.
SQD65
DC 0…10 V o
0…1000 Ω control signal
Selecting the flow charac-
teristic
Position of S1
Flow characteristic
Priority of signals
Features and benefits
Caution