Siemens RDG100KN Basic documentation CE1P3191en
Building Technologies Functions 22 Jun 2010
Modulating control: 3-position or PWM
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection (P01 = 2) Cooling mode with manual selection P01 = 2)
Y [%]
100
0
w
3181D1124a
T[°C]
XpH
Y1
YE
w
D
½ SDH ½ SDH
3181D105a
Y [%]
100
0
w
T[°C]
Y2
XpC
Heating and cooling mode (P01 = 4)
T[°C] Room temperature
w Room temperature setpoint
YE Control command “El heater"
(only ON/OFF)
Y1 Control command “Valve” (H)
(only PWM, not 3-position)
Y2 Control command “Valve” (C)
XpH Proportional band “Heating” (P30)
XpC Proportional band “Cooling” (P31)
X
dz
Dead zone (P33)
Y [%]
100
0
w
3181D114a
T[°C]
Y2
XpH
Y1
XpC
½
x
dz
½
x
dz
YE
w
D
½ SDH ½ SDH
w
D
Setpoint differential (P34)
The diagrams only show the PI thermostat’s proportional part.
Setting the sequence and the control outputs
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
Y1 can only be ON/OFF or PWM
Y2 can be ON/OFF, PWM or 3-position
YE can only be ON/OFF
Note:
Notes: