Siemens RDG100KN Room thermostat with KNX communications CE1N3191en
Building Technologies 01 Jun 2010
The thermostat's control parameters can be set to ensure optimum performance of
the entire system (see basic documentation P3191).
The parameters can be adjusted using
Local HMI
Synco ACS
ETS3 Professional (planned)
The control sequence may need to be set via parameter P01 depending on the
application. The factory setting is as follows:
Application Factory setting P01
2-pipe and chilled / heated ceiling, and 2-stage 1 = Cooling only
4-pipe, chilled ceiling and radiator 4 = Heating and cooling
Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P05.
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy.
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press the left and right buttons simultaneously for 6 sec to activate programming
mode, which is indicated on the display with "PrO
g
".
Programming mode remains active until thermostat identification is complete.
Use ETS3 Professional to assign the KNX group addresses of the RDG communi-
cation objects.
Each device has a unique KNX serial number inside the plastic housing.
An additional sticker with the same KNX serial number is enclosed in the packa-
ging box. This sticker is intended for installers for documentation purposes.
Disposal
This device is classified as waste electronic equipment under European Directive
2002/96/EC (WEEE) and may not be disposed of as unsorted municipal waste.
Adhere to all relevant national laws.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.
Control parameters
Control sequence
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX group
addresses
KNX serial number