Guidelines for Installing Networked Automation Systems in Buildings
7-24
SIMATIC NET Twisted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
Figure 7-6 Interrupting the Conduit at an Expansion Joint
Redundant Bus Cables
The installation of redundant bus cables involves special requirements. Redundant
cables should always be installed on separate cable racks to avoid simultaneous
damage by the same event.
Install Bus Cables Separately
To prevent accidental damage to bus cables, they should be clearly visible and
should be separate from all other wiring and cables. To improve EMC, it is often
advisable to install the bus cables in a separate cable channel or in conductive,
metal tubes. Such measures also make it easier to localize a faulty cable.