Technical Specifications
Industrial Ethernet OSM/ESM
76
C79000-Z8976-C068-04
Switching Properties of OSM/ESM
Number of learnable addresses Up to 12000
Aging time 40s (Default)
Latency
4
µ
s (measured at 75% load between two
ports operating at 100 Mbps)
Switching procedure Store and forward
Permitted Ambient Conditions/EMC
Operating temperature 0°C to +60°C (exception: OSM ITP 62-LD
with 0°C to 55°C)
Storage/transport temperature -40°C to +80°C
Relative humidity in operation 95% (no condensation)
Operating altitude Max. 2000 m
Noise emission EN 55081 Class A
Noise immunity EN 50082-2
Laserprotection Class 1 comply with IEC 60825-1
Mechanical Design
Dimensions (W x H x D) in mm 217 x 136.5 x 69
Weight in g 1400
Installation options Standard rail
S7-300 rail
Wall mounted
Installation in 19" cubicle
Only horizontal installation permitted
(ventilation slits top/bottom)
Degree of protection IP 20