Siemens Advance Network Gateway Bedienungsanleitung Seite 30

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 95
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 29
2000591-001 Installation 23
CE Installations, Continued
3. A split ferrite filter must be clamped to DataNET copper wire and
fixed immediately to the outside of the unit; use Siemens Applied
Automation part number 1173000-013 ferrite contained in the CE In-
stallation Kit. This is required to meet the Conducted Immunity re-
quirement for CE/EMC Heavy Industrial. All other CE/EMC Heavy
Industrial requirements are met without the use of a ferrite clamp.
4. Shielded Ethernet cable must be used for all Ethernet connections,
in and outside the GC, and coupled through the enclosure using a
shielded RJ-45 coupler; use Siemens Applied Automation part num-
ber 1183200-003 contained in the CE Installation Kit. A mounting
plate (Siemens Applied Automation part number 2020261-001) is
also available to accomplish this. If needed for Zone 1 installation,
Siemens Applied Automation part numbers 2017984-001 and
2017985-001 is available to maintain purge. If a PG gland is used to
make the 360-degree termination of the Ethernet shield at the enclo-
sure, the Installation Kit and other parts are not required.
Seitenansicht 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 94 95

Kommentare zu diesen Handbüchern

Keine Kommentare