Exception Codes
B-2
SIMATIC TI505/TI500 MODNIM User Manual
B.1 Exception Codes Supported by the MODNIM
T
able B-1
lists the subset of SIMA
TIC TI Exception Codes that are mapped
to the Modbus exception codes.
T
able B-1
Exception Codes
Exception
Code (hex)
Definition
00 The primitive is not implemented.
01 Data type is not defined in the attached device.
02 Data element location is out of range.
06 Device in wrong mode for primitive execution.
07 User program in device has disabled communications to NIM
(Lockout Bit)
0A Device fails to respond.
0B Primitive aborted due to fatal error condition in attached device.
0D Error encountered while executing the requested primitive.
10 The number of locations requested exceeds the maximum allowed.
15 Primitive not allowed while device is in local mode.
17 The attached device did not respond properly (communications
problem).
19 The resulting data element location formed by the starting address
plus the number of data elements to access, is out of range.
1A Communications has not been established with the attached
device.
1D The number of locations to access is zero.