Specifications
C-2
SIMATIC TI505/TI500 MODNIM User Manual
C.1 Environmental Specifications
The
Series 505 I/O subsystem is tested against some of the most stringent
standards in the world. T
able C-1 lists specifications that are common to
Series 505 I/O devices.
T
able C-1
Envir
onmental Specifications
Operating
T
emperature
0° to 60°
C (32
°
to
140
°F)
Storage Temperature
–40°
to +70
°
C (–40
°
to 158
°F)
Relative Humidity 5% to 95% non-condensing
Pollution Degree
2, IEC 664, 664A
Vibration
Sinusoidal
Random
IEC 68-2-6, Test Fc;
0.15 mm, peak-to-peak, 10–57 Hz;
1.0 g 57–150 Hz
NAVMAT P-9492 or IEC 68-2-34
Test Fdc with 0.04 g
2
/Hz, 80–350 Hz, and
3 dB/octave rolloff, 80–20 Hz and
350–2000 Hz at 10 min/axis
Impact Shock
IEC, 68-2-27, T
est Ea; Half sine, 15 g 11 ms
Electric Noise Immunity
Conducted noise: IEC 801, Part 4, Level 3
MIL STD 461B, Part 4; CS01, CS02, CS06
IEC 255-4
EEC 4517/79 Com(78) 766 Final, Part 4
IEEE 472, 2.5 kV
Radiated noise: IEC 801, Part 3, Level 3
MIL STD 461B, Part 4; RS01, RS02
Electrostatic discharge: IEC 801, Part 2, Level 4, (15 kV)
System Isolation Isolation (user-side to controller-side): 1500 Vrms
Torque for bezel screws
0.3 N-m (2.61 in.-lbs.) minimum
0.6 N-m (5.22 in.-lbs.) maximum
Corrosion Protection All parts are of corrosion resistant material or are
plated or painted as corrosion protection.
Agency Approvals
UL Listed (UL508 industrial control equipment)
CSA Certified (CSA142 process control equipment)
FM Approved (Class I, Div. 2, Hazardous locations)