Siemens EF 837 Series Spezifikationen Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 68
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
3BSE056248 53
Section 5 Maintenance/Replacement of
Faulty Units
Online Replacement of Unit
Replacement online entails adding or removing units in a controller without
disturbing the execution of the running application program. Units are connected to
the CEX-Bus and the electrical ModuleBus (S800 I/O).
CEX-Bus
Communication interfaces () Can be removed or replaced online
Restrictions apply; refer to the installation section
for each interface.
Base plates for CI8xx (TP8xx) It is not allowed to manipulate CEX bus base
plates in a powered and running system. Before
changing or removing a base plate, all CEX
modules on that segment must be removed.
ModuleBus
S800 I/O units Can be removed or replaced online. (Not S800L)
Module Terminal Units (MTUs) Must not be replaced online
Redundant CPUs
Processor unit Can be removed or replaced online by following a
specified sequence (see the next following pages)
Seitenansicht 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 67 68

Kommentare zu diesen Handbüchern

Keine Kommentare