Appendix B: CRC-16 Calculation
02/13 Modbus® RTU Serial Communications User Manual 65
A.20 Herculine Smart Actuator Value Register Map
Address
(hex)
Register
(decimal)
Parameter Name Access Notes
1AD0 46865 Position R FP 0-100% or 0-90 Degrees of Travel
1AD2 46867 Input R Floating Point 0-100%
1AD4 46869 Output R Floating Point 0-100%
1AD6 46871 Remote Setpoint R/W Floating Point 0-100%
1AD8 46873 Input Low Range R/W Floating Point 0-100%
1ADA 46875 Input High Range R/W Floating Point 0-100%
1ADC 46877 Relay #1 SP1 R/W Floating Point 0-100%
1ADE 46879 Relay #1 SP2 R/W Floating Point 0-100%
1AE0 46881 Relay #2 SP1 R/W Floating Point 0-100%
1AE2 46883 Relay #2 SP2 R/W Floating Point 0-100%
1AE4 46885 Relay #3 SP1 R/W Floating Point 0-100%
1AE6 46887 Relay #3 SP2 R/W Floating Point 0-100%
1AE8 46889 Relay #4 SP1 R/W Floating Point 0-100%
1AEA 46891 Relay #4 SP2 R/W Floating Point 0-100%
1AEC 46893 Deadband R/W Floating Point 0.2-5.0%
1AEE 46895 Deviation R Floating Point 0-100%
1AF0 46897 Reserved for future
1AF2 46899 Reserved for future
1AF4 46901 Reserved for future
1AF6 46903 Reserved for future
1AF8 46905 Reserved for future
1AFA 46907 Reserved for future
1AFC 46909 Alarm Status R Bit Packed Actuator Alarm / Relay Status
Bit 0 : Alarm / Relay 1
Bit 1 : Alarm / Relay 2
Bit 2 : Alarm / Relay 3
Bit 3 : Alarm / Relay 4
Bit 4 : Unused
Bit 5 : Stall Alarm
Bit 6 : Rivitz Failure
Bit 7 : Unused
0 : Alarm Off; 1 : Alarm On
1AFD 46910 Mode Status R/W Bit Packed Actuator Mode Status
Bit 0: Auto / Man Mode (0=Man; 1=Auto)
Bit 1 – 3 : Unused
Bit 4: Man Front Panel (0=Man; 1=Auto)
Bit 5: Man Ext Switch (0=Man; 1=Auto)
Bit 6 – 7 : Unused