Overview
• Analog outputs for SIMATIC S7-400
• For connection of analog actuators
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme specific infor-
mation was added.
For technical documentation on SIPLUS, see:
www.siemens.com/siplus-extreme
■
Ordering data
Order No.
SIPLUS SM 432 analog output module
Order number 6AG1 432-1HF00-4AB0
Order No. based on 6ES7 432-1HF00-0AB0
Range of ambient temperature 0 ... +60 °C
Conformal coating
Coating of the printed circuit boards
and the electronic components
Technical data
The technical data of the standard
product applies except for the envi-
ronmental conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permissi-
ble. No commissioning if condensa-
tion present.
Biologically active substances,
compliance with EN 60721-3-3
Class 3B2 mold and fungal spores
(excluding fauna). The supplied
plug covers must remain in place
over the unused interfaces during
operation!
Chemically active substances,
compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accor-
dance with EN60068-2-52 (degree
of severity 3). The supplied plug
covers must remain in place over
the unused interfaces during opera-
tion!
Mechanically active substances,
compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The sup-
plied plug covers must remain in
place over the unused interfaces
during operation!
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa
(+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
SIPLUS SM 432
analog output module
6AG1 432-1HF00-4AB0
(medial exposure)
8 outputs, floating, 13 bit
Accessories See SIMATIC S7-400 analog
output modules, page 6/74