Siemens Simatic M7-400 Bedienungsanleitung Seite 87

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 158
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 86
SIMATIC S7-400
Function modules
FM 455 controller module
6/87
Siemens ST 70 · 2013
Technical specifications (continued)
6
Input ranges (rated values),
resistance thermometers
Pt 100 Yes Yes
Thermocouple (TC)
for thermocouples Type B, J, K, R, S Type B, J, K, R, S
Temperature compensation
- internal temperature
compensation
Yes; Parameterizable Yes; Parameterizable
- external temperature c
ompensation with Pt100
Yes; Parameterizable Yes; Parameterizable
Resistance thermometer (RTD)
Characteristic linearization
- for resistance thermometer Pt100 (standard) Pt100 (standard)
Characteristic linearization
• Parameterizable Yes Yes
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples 200 m; 50 m at 80 mV and thermocouples
Analog outputs
Number of analog outputs 16
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current,
max.
25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
• 0 to 10 V Yes
-10 to +10 V Yes
Output ranges, current
• 0 to 20 mA Yes
-20 to +20 mA Yes
• 4 to 20 mA Yes
Connection of actuators
for voltage output
2-conductor connection
Yes
for current output
2-conductor connection
Yes
Load impedance
(in rated range of output)
• with voltage outputs, min. 1kΩ
with voltage outputs, capacitive load,
max.
F
• with current outputs, max. 500 Ω
• with current outputs, inductive load,
max.
1mH
Cable length
Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value creation
Measurement principle integrating integrating
Integrations and conversion time/
resolution per channel
Resolution with overrange
(bit including sign), max.
14 bit; 12 or 14 bit, parameterizable 14 bit; 12 or 14 bit, parameterizable
• Conversion time (per channel)
16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz;
for 14 bit: 100 ms for 50 and 60 Hz
16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz;
for 14 bit: 100 ms for 50 and 60 Hz
Settling time
for resistive load 0.2 ms 0.1 ms
for capacitive load
3.3 ms 3.3 ms
for inductive load
0.5 ms 0.5 ms
6ES7 455-0VS00-0AE0 6ES7 455-1VS00-0AE0
Kap_06_eng.book Seite 87 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Seitenansicht 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 157 158