Page 44 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
* Values shown are for illustration purposes only. Enter values which apply to your
particular installation.
! 2% factory set deadband, adjustable via P116
Setpoints Action When
ON OFF Status Alarm Relay
Level H or HH 85% 70% On On de-energizes Level rises to 85%
Off Off energizes Level falls to 70%
Level L or LL 15% 30% On On de-energizes Level falls to 15%
Off Off energizes Level rises to 30%
In bounds
!
80% 50% On On de-energizes Level falls to 78%
Off Off energizes Level rises to 82%
On On de-energizes Level rises to 52%
Off Off energizes Level falls to 48%
Out of bounds
!
80% 50% Off Off energizes Level falls to 78%
On On de-energizes Level rises to 82%
Off Off energizes Level rises to 52%
On On de-energizes Level falls to 48%
Rate of change +10% +5% Off Off de-energizes Fill rate increases to 10%/min
On On energizes Fill rate decreases to 5%/min
-10% -5% Off Off de-energizes Empty rate increases to 10%/min
On On energizes Empty rate decreases to 5%/min
Tem pera tu re 60 55 On On de-energizes Temperature rises to 60°C
Off Off energizes Temperature falls to 55°C
-30 -25 On On de-energizes Temperature falls to -30°C
Off Off energizes Temperature rises to -25°C
Pump 80% 20% On On energizes Start pump down on level at 80%
Off Off de-energizes Stop pump down on level at 20%
20% 80% On On energizes Start pump up on level at 20%
Off Off de-energizes Stop pump up on level at 80%