10 Controlling the drive
Control word 1 (STW1) and the main set-point (HSW) are sent to the drive
via the PROFIBUS interface. Status word 1 (ZSW1) and the main actual
value (HIW) are received from the drive.
The drive is started by sending the typical control word 047E, followed by
047F (edge of bit 0: ON). In order to stop the drive, word 047E should be
sent to the drive (edge of bit 0: OFF). The control word is sent together with
process data word 1 (PZD1) that should be specified in the variable table
VAT_1 (bit memory word MW0, refer to Fig. 10-1).
Status word 1 (ZSW1) is received from the drive (PZD1) and is transferred
into the bit memory word MW4. The MW4 can be taken from variable table
VAT_1 (refer to Fig. 10-1).
The main setpoint is sent, together with PZD2 to the drive - and the main
actual value is received from the drive in PZD2. The main set-point should
be specified in the variable table VAT_1 (bit memory word MW2, refer to
Fig. 10-1). The response - the main actual value - is saved in the MW6 and
can be taken from the variable table (refer to Fig. 10-1).
The frequency setpoint and actual value are normalized so that 4000(hex)
corresponds to 50Hz. The highest value that should be sent is 7FFF. The
normalization frequency (reference frequency) can be modified in P2000
(default, 50Hz).
Figure 10-1 Controlling the drive
Enter control word 1
Enter main setpoint
Read-out status word 1
Read-out actual
frequency