Software requirements
Chapter 3.
3. Software requirements
eWON configuration software:
The eWON is configured through its web server. All you need is a standard Web Browser
software like Internet Explorer or Firefox.
Additionally we suggest downloading the eBuddy utility from our website
http://support.ewon.biz/
This utility allows you to list all the eWONs on your network and to change the default IP address
of an eWON to match your LAN IP address range. With eBuddy you can also easily upgrade the
firmware or make a backup of your eWON (if required).
eWON Firmware Version
The screen-shots of this guide reflect firmware version 6.4 S2 (2012), but you can expect the
basic principles to remain the same in earlier/later versions.
4. PLC protocol compatibility
The table below shows the Siemens protocols that are supported and, for each of those, which IO
Server you need to use inside the eWON to connect your Siemens PLC.
4.1 eWON with MPI port
PLC-Family
MPI/Profibus
protocols
PPI protocol
(over MPI port)
Ethernet
ISOTCP
(Ethernet link)
EWON
IO Server name
S7-300 (*) YES NO YES S73&400 (*)
S7-400 (*) YES NO YES S73&400 (*)
S7-1200 (*) NO NO YES S73&400 (*)
S7-200 NO YES YES S7200
Table – MPI port device protocol compatibility
4.2 eWON with serial port
PLC-Family
MPI/Profibus
protocols
PPI protocol
(over serial link)
Ethernet
ISOTCP
(Ethernet link)
EWON
IO Server name
S7-300 (*) NO NO YES S73&400 (*)
S7-400 (*) NO NO YES S73&400 (*)
S7-1200 (*) NO NO YES S73&400 (*)
S7-200 NO YES YES S7200
Table – Serial port device protocol compatibility
(*) Note that the S7-300, 400 & 1200 families are addressed in a separate guide (different IO
Server and syntax). This guide has reference AUG-048 and is available here:
http://wiki.ewon.biz/Support/07_Documentations/AUG
Polling Data Registers from Siemens S7-200 PLC Series (How to) Page 5/21