5 Performance Data / Operation
B41
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
Example
The CP 343-1 Advanced can transfer a maximum of 41 array elements of the type
DWORD or REAL with a read job since each element of the type DWORD or
REAL occupies four bytes.
5.9 Characteristics of the C-PLUG
The flash area allows a limited number of write cycles.
S Number of write cycles: approx. 100 000
Recommendation: You should therefore avoid writing data cyclically.
5.10 Characteristic data of the integrated switch
Learning addresses / deleting addresses (aging time)
The switch integrated in the CP (PROFINET interface) reads the source addresses
in the data packets. The switch therefore learns the addresses of the end devices
connected via a port.
If the switch receives a data packet, it directs this packet only to the port via which
the appropriate DTE can be obtained.
The switch monitors the age of the learned addresses. Addresses that exceed the
“aging time” are deleted. The aging time is 5 minutes.
Ports can be deactivated individually
The ports of the switch integrated in the CP and the gigabit interface can be
deactivated individually in STEP 7 / HW Config. This can, for example, be used for
service purposes.
To do this, open the properties dialog of the relevant port and select the “disabled”
setting under “Options > Transfer medium / duplex”.
The port is turned off completely when it is deactivated. The corresponding LED on
the device (for example P1) is then turned off.
Seitenansicht 40