Siemens SIMATIC NET PROFIBUS Betriebsanleitung Seite 130

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 490
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 129
Passive Components for RS-485 Networks
4-32
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
4.3 Bus Connectors
Uses
Using the bus connector for SIMATIC NET PROFIBUS:
S Nodes with an electrical 9-pin sub-D interface complying with EN 50170 can be
connected directly to the SIMATIC NET PROFIBUS cables
S Electrical segments or individual nodes can be connected to the optical link
module (OLM, OBT).
S Nodes or programming devices can be connected to a repeater.
Note
The integrated bus terminators and the mechanical specifications of the SIMATIC
NET bus connectors are tailored to the SIMATIC NET PROFIBUS cables (cable
type A of the PROFIBUS standard EN 50170-1-2). Fitting bus connectors to
cables with different electrical or mechanical properties can cause problems during
operation!
Seitenansicht 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 489 490

Kommentare zu diesen Handbüchern

Keine Kommentare