Siemens SPC3 Spezifikationen Seite 29

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 38
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 28
Introduction To ProfiBus DP
___________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com
29
Diag_Data Response Telegram DU Byte 3 – Station_status_3
Bit DIAGNOSTIC
0-6
Reserved.
7 Diag.Ext_Diag_Overflow:
Set if there is more diagnostic
information than specified in Ext_Diag_Data. For example, slave
sets if slave has more diagnostics than it can enter into its send
buffer. Set by master if slave sends more diagnostic information
than it can enter into its diagnostic buffer.
Diag_Data Response Telegram DU Byte 4 (Para Master Address)
Bit DIAGNOSTIC
0-7 Diag.Master_Add:
The master’s address that parameterized this
slave is entered here. If no master has parameterized this slave,
then the DP Slave inserts 255 here (FF without parameterization).
Diag_Data Response Telegram DU Byte 5 - Ident_Number High Byte
Bit DIAGNOSTIC
0-7
Manufacturer Identification Number High byte for ID & verification
Diag_Data Response Telegram DU Byte 6 - Ident_Number Low Byte
Bit DIAGNOSTIC
0-7
Manufacturer Identification Number Low byte for ID & verification.
DU Bytes 7-32 (or optionally up to 244 bytes) contain DP-Slave specific
diagnostic information structured in blocks according to format type: device-
related, identifier-related, and channel-related.
Diag_Data Response Telegram DU Byte 7-X – Ext_Diag_Data
Bit DIAGNOSTIC
0-7
Ext_Diag_Data (see formats below, refer to your model
specifications for extended diagnostic data).
Ext_Diag_Data - Application Specific Diagnostics
The master can store user-related diagnostics in the following three
different formats:
device related
,
identifier related
, and
channel related
.
Device-Related Diagnostic
This information is device-related and can be coded in any form. It can
be used to indicate general diagnostic information such as: over-
temperature, under-voltage, over-voltage, etc.
Device Related Diagnostic Byte 1 of X – Header Byte
76543210
00XXXXXX
Bits 7,6 = 00 Bits 5-0 = Block Length in bytes including header byte 2
to header byte 63.
Device Related Diagnostic Byte 2 of X – Diagnostic Field Byte(s)
76543210
XXXXXXXX
Diagnostic coding is device-specific and can be coded as desired.