Issue 11/04 6 Commissioning
SINAMICS G110
Operating Instructions (Compact)
19
6.2.4 Digital output (DOUT)
P0731 =...
Function of digital output 0*
Defines source of digital output 0.
P0748 = 0
Invert digital output
Allows the signals to be output to be inverted.
Status of DOUT at logically active signal (0 = Open; 1 = Closed)
Frequent settings: Active Status
0 Not Active
1 Active
2 Drive ready
3 Drive ready to run
4 Drive running
5 Drive fault active
6 OFF2 active
7 OFF3 active
8 Switch on inhibit active
9 Drive warning active
10 Deviation between f
set
and f
act
< 3 Hz
11 PZD control (P0700=5)
12 Act. Freq P1082 (f
max
)
13 Warning: Motor current limit
14 Motor holding brake active*
15 Motor overload
-
-
High
High
High
High
Low
Low
High
High
High
High
High
High
High
High
0 (always)
1 (always)
1
1
1
0
0
0
1
1
1
1
1
0
1
0
*Note: Motor holding brake active means the brake is open.
-1
0
1
Invert digital outputs
0 ... 1
P0748 (0)
CO/BO: State of digital outputs
r0747
r0747
2
1
.0
DOUT channel
Function of digital output 0
0 ... 22
P0731 (5)
0
23
...
Functions
DOUT+
DOUT-
24 V DC 50 mA
6.2.5 Selection of frequency setpoint
P1000 G110 AIN G110 USS Settings
0 X X
1 X X see 6.2.7
2 X – see 6.2.6
3 X X see 6.2.8
P1000 =...
Selection of frequency setpoint
0 No main setpoint
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
5 USS
5 – X see 6.2.1