Issue 11/04 Warnings, Cautions and Notes
SINAMICS G110 Operating Instructions (Compact)
Operating Instructions (Compact)
3
NOTES
¾ This equipment is capable of providing internal motor overload protection in
accordance with UL508C section 42 (refer to P0610 and P0335). I
2
t monitoring
is ON by default.
Motor overload protection can also be provided using an external PTC via a
digital input.
¾ This equipment is suitable for use in a circuit capable of delivering not more
than 10,000 symmetrical amperes (rms), for a maximum voltage of 230 V
when protected by an H or K type fuse, a circuit breaker or self-protected
combination motor controller.
¾ Use Class 1 75 °C copper wire only with the cross-sections as specified in
Section 2.1
¾ The maximum permissible ambient temperature is, depending on the
equipment, 40 °C or 50 °C (refer to Section 2.1).
¾ Before installing and commissioning, please read these safety instructions and
warnings carefully and all the warning labels attached to the equipment.
¾ Make sure that the warning labels are kept in a legible condition and replace
missing or damaged labels.