Communication
6.5 Communication via PROFINET
Control Units CU240S
Operating Instructions, 10/2007, A5E00766042B AC
173
6.5.4 PROFInet Configuration Example with SIMATIC S7
Prerequisites
To integrate a SINAMICS G120 inverter in SIMATIC S7 control system, the following
requirements should be fulfilled:
Prerequisites for standard inverters
STEP 7 V5.4, SP1 is installed on the engineering station
In HW Config, the following components are disposed:
One of the following CPUs
CPU 315-2 PN/DP with firmware at least 2.5.1
CPU 317-2 PN/DP with firmware at least 2.5.1
CPU 319-3 PN/DP
A SIMATIC control system with a PROFINET sub-network, e.g. SIMATIC 300
SINAMICS G120 inverters are available as PROFINET I/O device in the hardware
catalog.
Prerequisites for PROFIsafe via Profinet
STEP 7 V5.4, SP2 is installed on the engineering station
In HW Config, the following components are disposed:
One of the following CPUs
CPU 315F-2 PN/DP with firmware at least 2.5.1
CPU 317F-2 PN/DP with firmware at least 2.5.1
CPU 319F-3 PN/DP
A SIMATIC control system with a PROFINET sub-network, e.g. SIMATIC 300
SINAMICS G120 inverters are available as PROFINET I/O device in the hardware
catalog.
If the G120 is not available, the GSDML V2.0 has to be installed. It can be downloaded and
installed from the internet under the following link:
http://support.automation.siemens.com/WW/view/de/22339653/133100
Installing the GSDML V2.0 file
1. Save the GSDML V2.0 file on your system and save the path.
2. Choose in the menu "Options > Install GSD File".
A dialog box is displayed.
3. Add the relevant path to the GSDML V2.0 file and confirm with OK.