Siemens APOGEE™ FLN (P1) Communication Kit
3-4
For more information visit:
www.EatonElectrical.com
MN04008002E
February 2006
Bus Biasing
Bus biasing is required to ensure faultless communication between devices at RS-485 bus.
Bus biasing makes sure that the bus state has proper potential when no one is transmitting.
Without biasing faulty messages can be detected when the bus is in idle state. RS-485 bus
state should be from +0.200 to +7V or -0.200 to -7V. Illegal bus state is from -0.200 to 0.200V.
Table 3-1: Bias Resistor Size vs. Number of Nodes
Failsafe Biasing in OPTCB Option Board
Connect resistor biasing resistors between PIN 2 – PIN 4 and PIN 3 – PIN 5. See
Figure 3-7
.
Figure 3-7: Connecting Resistor Biasing
National Semiconductor (www.national.com) has a very good application note,
Failsafe
Biasing of Differential Buses
(AN-847.PDF), concerning this problem.
Number of Nodes Bias Resistance
2 – 5 1.8k ohm
5 – 10 2.7k ohm
11 – 20 12k ohm
21 – 30 18k ohm
31 – 40 27k ohm