Chapter 9. Configuring the I/O Driver with the Power Tool 133
the failed device, it ignores the Retries and only makes one attempt. If the
attempt is successful, the driver recovers all datablocks on the device and
marks them ready for messages.
By using QuickFail, the driver saves time and bypasses the problem device,
thereby increasing its efficiency.
See Also
Adding and Modifying Devices | Feature: QuickFail Logic
Adding and Modifying Datablocks
Datablocks define areas in PLC memory you want the SI7 driver to access.
Example
Reply Timeout = 15 (15 seconds)
Retries = 5
Delay Time = 5:00(5 minutes)
Backup Device = none
Global timeout = 10 (10 seconds)
The driver attempts to send a message to the process hardware. After 15 seconds, the device
still has not responded so the driver re-sends the message.
SIMATIC NET determines it is able to send another message. Consequently, the driver tries
to send the message again. Assuming that it is able to send data for all retries, the driver sends
the request 6 times (the first time and then the 5 retries) with 15-second intervals between each
attempt.
Each attempt fails; consequently, the driver marks the datablock as failed. If the driver has
messages for other datablocks on the same device, it sends them only once without retries.
The driver waits 5 minutes before attempting to re-establish communication with the failed
device.