228 Siemens Simatic S7 Driver Online Help
If you cannot see the remote server from Microsoft Explorer or by using the Ping
program
You have a networking problem. You may want to speak to your network
administrator.
If you were running the Power Tool and you changed the server location
[1] Exit the Power Tool and restart it. If this is not the problem, proceed with the
following steps.
[2] Physically go to the server and verify that it started successfully.
[3] If the server does not start, refer to My driver does not load.
[4] If the server does start, leave the server running and try to connect to it from
another computer.
See Also
Troubleshooting
I am receiving old data in my display
Data returned from a datablock read comes directly from I/O driver memory. The
data in memory updates when the driver polls. A read from SAC or a picture does not
prompt the I/O driver to poll for data. If you enter a scan time that is longer than the
datablock’s access time, the I/O driver always returns old data and the driver flags the
data quality as NO_DATA.
To resolve this problem, select a scan time that is shorter than the access time and
enter an access time that is longer than the phase and the primary or secondary poll
rate.
Example
To receive up-to-date data, you could set the poll rate, access time, and scan time as follows:
Poll rate: 5 seconds
Access time: 15 seconds