Item Number 125-3201, Rev. 012 SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual
SED2 VFD Startup, Operation, and Maintenance Manual 90 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Drive Reaction F0080, Analo
Troubleshooting Siemens Building Technologies, Inc. 91 Error Cause Diagnosis/Remedy Drive Reaction F0452, Belt failure detected Load condition chan
SED2 VFD Startup, Operation, and Maintenance Manual 92 Siemens Building Technologies, Inc. Warning Messages Error Cause Diagnosis and Remedy Drive
Troubleshooting Siemens Building Technologies, Inc. 93 Error Cause Diagnosis and Remedy Drive Reaction A0505, SED2 I2t Warning level exceeded. The
SED2 VFD Startup, Operation, and Maintenance Manual 94 Siemens Building Technologies, Inc. Error Cause Diagnosis and Remedy Drive Reaction A0910,
Troubleshooting Siemens Building Technologies, Inc. 95 Error Cause Diagnosis and Remedy Drive Reaction A0921, Analog output parameters not set pro
SED2 VFD Startup, Operation, and Maintenance Manual 96 Siemens Building Technologies, Inc. Replacement Parts Replacement Part Description Part Num
Repair Siemens Building Technologies, Inc. 97 Repair Only Siemens service departments, repair centers authorized by Siemens Building Technologies, I
SED2 VFD Startup, Operation, and Maintenance Manual 98 Siemens Building Technologies, Inc. Technical Specifications Table 9. Drive Specifications.
Technical Specifications Siemens Building Technologies, Inc. 99 Drive Specifications Description • Under-voltage • Over-voltage • Overload • Groun
How to Use This Manual Siemens Building Technologies, Inc. 1 How To Use This Manual This manual is written for users of Siemens Building Technologie
SED2 VFD Startup, Operation, and Maintenance Manual 100 Siemens Building Technologies, Inc. Appendix A: Parameters, Defaults, and Settings Paramete
Appendix A: Parameters, Defaults, and Settings Siemens Building Technologies, Inc. 101 Parameter Description Unit User Setting Min Default Max Acce
SED2 VFD Startup, Operation, and Maintenance Manual 102 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max
Appendix A: Parameters, Defaults, and Settings Siemens Building Technologies, Inc. 103 Parameter Description Unit User Setting Min Default Max Acce
SED2 VFD Startup, Operation, and Maintenance Manual 104 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max
Appendix A: Parameters, Defaults, and Settings Siemens Building Technologies, Inc. 105 Parameter Description Unit User Setting Min Default Max Acce
SED2 VFD Startup, Operation, and Maintenance Manual 106 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max
Appendix A: Parameters, Defaults, and Settings Siemens Building Technologies, Inc. 107 Parameter Description Unit User Setting Min Default Max Acce
SED2 VFD Startup, Operation, and Maintenance Manual 108 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max
Appendix A: Parameters, Defaults, and Settings Siemens Building Technologies, Inc. 109 Parameter Description Unit User Setting Min Default Max Acce
SED2 VFD Startup, Operation, and Maintenance Manual 2 Siemens Building Technologies, Inc. Manual Notations Notation Symbol Meaning DANGER: Indicat
SED2 VFD Startup, Operation, and Maintenance Manual 110 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max
SED2 VFD Startup, Operation, and Maintenance Manual 111 Siemens Building Technologies, Inc. Appendix B: SED2 Point Maps Table 10. SBT P1 Point Cros
SED2 VFD Startup, Operation, and Maintenance Manual 112 Siemens Building Technologies, Inc. Table 10. SBT P1 Point Cross Reference to SED2. Point N
Appendix B: SED2 Point Cross-Reference Siemens Building Technologies, Inc. 113 Table 10. SBT P1 Point Cross Reference to SED2. Point No. Point Type
SED2 VFD Startup, Operation, and Maintenance Manual 114 Siemens Building Technologies, Inc. Table 11. JCI N2 Point Cross Reference to SED2. On T
Appendix B: SED2 Point Cross-Reference Siemens Building Technologies, Inc. 115 Table 11. JCI N2 Point Cross Reference to SED2. On Text Off Text
SED2 VFD Startup, Operation, and Maintenance Manual 116 Siemens Building Technologies, Inc. Table 11. JCI N2 Point Cross Reference to SED2. On Te
SED2 VFD Startup, Operation, and Maintenance Manual 117 Siemens Building Technologies, Inc. Glossary Access Level The degree of authorization a user
SED2 VFD Startup, Operation, and Maintenance Manual 118 Siemens Building Technologies, Inc. EMI Electromagnetic Interference. Fixed Frequency Frequ
Glossary Siemens Building Technologies, Inc. 119 NEMA Type 12/IP54 IP54 is a European enclosure rating; there is no equivalent North American rating
Safety Instructions Siemens Building Technologies, Inc. 3 Safety Instructions General The following general guidelines are provided for your safety,
SED2 VFD Startup, Operation, and Maintenance Manual 120 Siemens Building Technologies, Inc. Parameter Index/Indexes Subsets of closely related infor
Glossary Siemens Building Technologies, Inc. 121 Slip Compensation Dynamically adjusts the output frequency of the SED2 so that the motor speed is k
SED2 VFD Startup, Operation, and Maintenance Manual Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-
SED2 VFD Startup, Operation, and Maintenance Manual 4 Siemens Building Technologies, Inc. Environmental Compatibility and Disposal The SED2s are dev
Mechanical Installation Siemens Building Technologies, Inc. 5 Mechanical Installation Product Numbers The following chart shows SED2 product number
SED2 VFD Startup, Operation, and Maintenance Manual 6 Siemens Building Technologies, Inc. Frame Sizes The following chart shows SED2 IP20 and NEMA T
Mechanical Installation Siemens Building Technologies, Inc. 7 Interpreting Serial Numbers and Date Codes Each SED2 has a manufacturing/serial number
SED2 VFD Startup, Operation, and Maintenance Manual 8 Siemens Building Technologies, Inc. Output Ratings Table 1 shows SED2 product numbers and the
Mechanical Installation Siemens Building Technologies, Inc. 9 Table 1. SED2 Product Numbers and Output Ratings. (Continued) Product Number Output
SED2 VFD Startup, Operation, and Maintenance Manual 10 Siemens Building Technologies, Inc. Accessories SED 2 accessories include the following: Glan
Mechanical Installation Siemens Building Technologies, Inc. 11 Environmental Conditions Install the SED2 in a heated, indoor-controlled environment
SED2 VFD Startup, Operation, and Maintenance Manual 12 Siemens Building Technologies, Inc. Dimensions and Mounting for IP20 SED2s Overall Dimensions
Mechanical Installation Siemens Building Technologies, Inc. 13 Mounting Dimensions Frame Size AFrame Size BFrame Size CFrame Size DFrame Size EFrame
SED2 VFD Startup, Operation, and Maintenance Manual 14 Siemens Building Technologies, Inc. Gland Plate Installation and Conduit Connections CAUTIO
Mechanical Installation Siemens Building Technologies, Inc. 15 Frame Size B Frame Size C.90(22.8).90(22.8).74(18.8)1.10(28)1.10(28).74(18.8)GroundVF
SED2 VFD Startup, Operation, and Maintenance Manual 16 Siemens Building Technologies, Inc. 20 21 22 23 24 2529 3017 26 27 2812 13 14 15 1610 116789
Mechanical Installation Siemens Building Technologies, Inc. 17 Dimensions and Mounting for NEMA Type 1 SED2s Overall Dimensions and Mounting Specifi
SED2 VFD Startup, Operation, and Maintenance Manual 18 Siemens Building Technologies, Inc. Mounting Dimensions 9.3(235)Frame Size AFrame Size BFrame
Mechanical Installation Siemens Building Technologies, Inc. 19 Dimensions and Mounting for IP54, NEMA Type 12 SED2s Overall Dimensions and Mounting
SED2 Variable Frequency Drives Startup, Operation, and Maintenance Manual
SED2 VFD Startup, Operation, and Maintenance Manual 20 Siemens Building Technologies, Inc. Mounting Dimensions Frame Size BFrame Size C0.19(4.8)9.1(
Mechanical Installation Siemens Building Technologies, Inc. 21 Mounting Instructions There must be a clearance of at least 5-7/8 inches (150 mm) in
SED2 VFD Startup, Operation, and Maintenance Manual 22 Siemens Building Technologies, Inc. Electrical Installation DANGER: • To ensure safe opera
Electrical Installation Siemens Building Technologies, Inc. 23 Extended Storage: Conditioning of Capacitors After an extended period of storage, rec
SED2 VFD Startup, Operation, and Maintenance Manual 24 Siemens Building Technologies, Inc. Input Power and Motor Connections DANGER: • Make certa
Electrical Installation Siemens Building Technologies, Inc. 25 Operation in Ungrounded Systems IP20 and NEMA Type 1 SED2s can operate in ungrounded
SED2 VFD Startup, Operation, and Maintenance Manual 26 Siemens Building Technologies, Inc. 123VFD0061R1 Figure 9. Disconnecting Y Capacitor in SED2
Electrical Installation Siemens Building Technologies, Inc. 27 M6T30Torx screwdriverVFD0063R1 Figure 11. Disconnecting Y Capacitor in SED2 Frame Si
SED2 VFD Startup, Operation, and Maintenance Manual 28 Siemens Building Technologies, Inc. Access to Connection Terminals To access input power and
Electrical Installation Siemens Building Technologies, Inc. 29 1VFD0068R1 Figure 15. Removing Cover on Frame Sizes B and C. 312564VFD0069R1 Figu
SED2 VFD Startup, Operation, and Maintenance Manual 30 Siemens Building Technologies, Inc. 234156VFD0070R1 Figure 17. Accessing Connection Terminal
Electrical Installation Siemens Building Technologies, Inc. 31 Motor Frequency and Unit of Measurement DIP Switches In all versions of the SED2, DIP
SED2 VFD Startup, Operation, and Maintenance Manual 32 Siemens Building Technologies, Inc. Input Power and Motor Terminal Layout DANGER: The follo
Electrical Installation Siemens Building Technologies, Inc. 33 L1 L2 L3 DC- DC+B+DCR+B- U V WVFD0073R1(Ground)PE(Ground) Figure 21. Input Power and
SED2 VFD Startup, Operation, and Maintenance Manual 34 Siemens Building Technologies, Inc. Tightening Torque for Input Power and Motor Connections
Electrical Installation Siemens Building Technologies, Inc. 35 Table 6. Cable Cross-Sections for Input Voltage Range 3Ø AC 380V through 480V. Inpu
SED2 VFD Startup, Operation, and Maintenance Manual 36 Siemens Building Technologies, Inc. Table 7. Cable Cross-Sections for Input Voltage Range 3
Electrical Installation Siemens Building Technologies, Inc. 37 Input Power Connection DANGER: • As supplied, the SED2 must be grounded (per IEC 5
SED2 VFD Startup, Operation, and Maintenance Manual 38 Siemens Building Technologies, Inc. Motor Cable Length Maximum motor cable length is 164 ft (
Electrical Installation Siemens Building Technologies, Inc. 39 Motor Connection (Wye "Y"/Star or Delta Configuration) DANGER: Do not us
NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Bu
SED2 VFD Startup, Operation, and Maintenance Manual 40 Siemens Building Technologies, Inc. Direction of Motor Rotation To change the direction of mo
Electrical Installation Siemens Building Technologies, Inc. 41 Motor Overload Protection WARNING: The SED2 is capable of providing internal motor
SED2 VFD Startup, Operation, and Maintenance Manual 42 Siemens Building Technologies, Inc. Connection of Multiple Motors The SED2 can control severa
Electrical Installation Siemens Building Technologies, Inc. 43 Analog Input DIP Switches WARNING: When using analog inputs, the DIP switches must
SED2 VFD Startup, Operation, and Maintenance Manual 44 Siemens Building Technologies, Inc. VFD0146R1DIP SWITCHES20 21 22 23 24 2529 3017 26 27 281
Electrical Installation Siemens Building Technologies, Inc. 45 NOTE: 1. Use only shielded cables for control cables. 2. Route control cables in se
SED2 VFD Startup, Operation, and Maintenance Manual 46 Siemens Building Technologies, Inc. Drive ParametersP0003P0010r0026r0039 - P0040P0100r0206 -
Electrical Installation Siemens Building Technologies, Inc. 47 Analog and Digital I/O Control Terminal Connections Figures 31 through 35 show typica
SED2 VFD Startup, Operation, and Maintenance Manual 48 Siemens Building Technologies, Inc. VFD0049R11234DIN7121112DIN8 Figure 33. Connection of An
Parameters Siemens Building Technologies, Inc. 49 Parameters Overview The SED2 uses parameters to define the required operating characteristics, suc
SED2 VFD Startup, Operation, and Maintenance Manual 50 Siemens Building Technologies, Inc. The following indexes are associated with P0700, P1000, a
SED2 Operator Panels Siemens Building Technologies, Inc. 51 SED2 Operator Panels Overview The SED2 includes the Basic Operator Panel (BOP) mounted
SED2 VFD Startup, Operation, and Maintenance Manual 52 Siemens Building Technologies, Inc. Advanced Operator Panel (AOP) For information on the AOP,
SED2 Operator Panels Siemens Building Technologies, Inc. 53 Operator Panel/Button Function Description Access to parameters Press this pushbutton t
SED2 VFD Startup, Operation, and Maintenance Manual 54 Siemens Building Technologies, Inc. NOTES: 1. If you attempt to modify a parameter that cann
Commissioning Siemens Building Technologies, Inc. 55 Commissioning WARNING: • Only authorized personnel trained in the setup, installation, commi
SED2 VFD Startup, Operation, and Maintenance Manual 56 Siemens Building Technologies, Inc. Motor Nameplate Data for Parameter Settings You can modif
Commissioning Siemens Building Technologies, Inc. 57 Prerequisites to Startup Procedure To ensure reliable SED2 operation and to avoid any extra cos
SED2 VFD Startup, Operation, and Maintenance Manual 58 Siemens Building Technologies, Inc. ( ) 5. Inspect the security of the input power wi
Commissioning Siemens Building Technologies, Inc. 59 ( ) 13. Record any other connections to the SED2 by terminal number to determine if spe
Table of Contents Siemens Building Technologies, Inc. i Table of Contents How To Use This Manual ...
SED2 VFD Startup, Operation, and Maintenance Manual 60 Siemens Building Technologies, Inc. DANGER: Wait for 5 minutes. Always wait 5 minutes after
Commissioning Siemens Building Technologies, Inc. 61 Quick Commissioning Procedure Parameter P0010 is the Commissioning Parameter Filter. It allows
SED2 VFD Startup, Operation, and Maintenance Manual 62 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default Quick Co
Commissioning Siemens Building Technologies, Inc. 63 Parameter Description Action Setting/ Default P0304 * Rated Motor Voltage 10V to 2000V Rat
SED2 VFD Startup, Operation, and Maintenance Manual 64 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default P0308 *,
Commissioning Siemens Building Technologies, Inc. 65 Parameter Description Action Setting/ Default P0311 * Rated Motor Speed 0 to 40,000 1/min
SED2 VFD Startup, Operation, and Maintenance Manual 66 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default Selectio
Commissioning Siemens Building Technologies, Inc. 67 Parameter Description Action Setting/ Default P1000[0] ** Selection of Frequency Setpoint (
SED2 VFD Startup, Operation, and Maintenance Manual 68 Siemens Building Technologies, Inc. Parameter Description Action Setting/ Default P1080 Mi
Commissioning Siemens Building Technologies, Inc. 69 Parameter Description Action Setting/ Default Ramp-down Time 0s to 650s 3. 1. Press to a
SED2 VFD Startup, Operation, and Maintenance Manual ii Siemens Building Technologies, Inc. Ungrounded Systems and Y Capacitor...
SED2 VFD Startup, Operation, and Maintenance Manual 70 Siemens Building Technologies, Inc. Additional Parameter Settings NOTE: If Display Selection
Commissioning Siemens Building Technologies, Inc. 71 Parameter Description Action Setting/ Default Motor Current: Flying Start Defines search cu
SED2 VFD Startup, Operation, and Maintenance Manual 72 Siemens Building Technologies, Inc. Automatic Restart CAUTION: Setting 2 through 5 can cau
Commissioning Siemens Building Technologies, Inc. 73 Parameter Description Action Setting/ Default P1211 Number of Restart Attempts Specifies nu
SED2 VFD Startup, Operation, and Maintenance Manual 74 Siemens Building Technologies, Inc. Vdc Controller Parameter Description Action Setting/ De
Commissioning Siemens Building Technologies, Inc. 75 Reset to Factory Defaults Parameter Description Action Setting/ Default Reset to Factory Defa
SED2 VFD Startup, Operation, and Maintenance Manual 76 Siemens Building Technologies, Inc. Network Communications Table 8 lists the parameters requ
Commissioning Siemens Building Technologies, Inc. 77 Changing Individual Parameter Digits To quickly change the value of a parameter, modify the ind
SED2 VFD Startup, Operation, and Maintenance Manual 78 Siemens Building Technologies, Inc. Maintenance Perform SED2 maintenance semi-annually. Estim
Maintenance Siemens Building Technologies, Inc. 79 • There should be no mechanical whining sound made from the fan 3. Close unit. 4. Remove lockou
Table of Contents Siemens Building Technologies, Inc. iii Additional Parameter Settings... 70 Flying Start
SED2 VFD Startup, Operation, and Maintenance Manual 80 Siemens Building Technologies, Inc. Troubleshooting Reading Faults • OK FAULT (r0052, bit 3)
Troubleshooting Siemens Building Technologies, Inc. 81 • For example: If the SED2 trips on undervoltage and then receives an external trip before t
SED2 VFD Startup, Operation, and Maintenance Manual 82 Siemens Building Technologies, Inc. Troubleshooting the Operator Panel If the display shows P
Troubleshooting Siemens Building Technologies, Inc. 83 Troubleshooting Using the Operator Panel NOTE: The voltage and current range of the SED2 mus
SED2 VFD Startup, Operation, and Maintenance Manual 84 Siemens Building Technologies, Inc. Fault Codes Error Cause Diagnosis/Remedy Drive Reaction
Troubleshooting Siemens Building Technologies, Inc. 85 Error Cause Diagnosis/Remedy Drive Reaction F0002, Overvoltage • DC link voltage (r0026) e
SED2 VFD Startup, Operation, and Maintenance Manual 86 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Drive Reaction F0004, SED2
Troubleshooting Siemens Building Technologies, Inc. 87 Error Cause Diagnosis/Remedy Drive Reaction F0021, Ground fault The ground fault occurs if t
SED2 VFD Startup, Operation, and Maintenance Manual 88 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Drive Reaction F0041, Moto
Troubleshooting Siemens Building Technologies, Inc. 89 Error Cause Diagnosis/Remedy Drive Reaction (Continued) F0041, Motor data identification fa