Item Number 125-3214, Rev. 010 SED2 Variable Frequency Drives Parameter Reference Guide
SED2 VFD Parameter Reference Guide The following indexes are associated with P0700, P1000, and digital input and output parameters: IN000 (AUTO), 1st
SED2 VFD Parameter Reference Guide 92 Siemens Building Technologies, Inc. P2101[3] Stop reaction value Level 3 Min: 0 Def: 0 Max: 5 Unit: - Det
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 93 P2111 Total number of warnings Level 3 Min: 0 Def: 0 Max: 4 Unit: -
SED2 VFD Parameter Reference Guide 94 Siemens Building Technologies, Inc. P2156 Delay time of threshold freq f_1 Level 3 Min: 0 Def: 10 Max: 100
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 95 P2181 Belt failure detection mode Level 3 Min: 0 Def: 0 Max: 6 Unit:
SED2 VFD Parameter Reference Guide 96 Siemens Building Technologies, Inc. P2182 Belt threshold frequency 1 Level 3 Min: 0.00 Def: 5.00 Max: 650.
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 97 P2183 Belt threshold frequency 2 Level 3 Min: 0.00 Def: 30.00 Max: 65
SED2 VFD Parameter Reference Guide 98 Siemens Building Technologies, Inc. P2188 Lower torque threshold 2 Level 3 Min: 0.0 Def: 0.0 Max: 99999.0
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 99 r2197 CO/BO: Monitoring word 1 Level 3 Min: - Def: - Max: - Unit: -
SED2 VFD Parameter Reference Guide 100 Siemens Building Technologies, Inc. P2200[2] BI: Enable PID controller Level 2 Min: 0:0 Def: 0:0 Max: 400
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 101 P2201 Fixed PID setpoint 1 Level 3 Min: -200.00 Def: 0.00 Max: 200.0
P0004 Parameter Filters/Categories Siemens Building Technologies, Inc. 3 P0004 Parameter Filters/Categories Quick Commissioning (P0010=1) Parameter
SED2 VFD Parameter Reference Guide 102 Siemens Building Technologies, Inc. Dependency: P2000=1 is required in user access level 2 to enable setpoin
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 103 P2206 Fixed PID setpoint 6 Level 3 Min: -200.00 Def: 50.00 Max: 200.
SED2 VFD Parameter Reference Guide 104 Siemens Building Technologies, Inc. P2212 Fixed PID setpoint 12 Level 3 Min: -200.00 Def: 110.00 Max: 200
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 105 P2217 Fixed PID setpoint mode - Bit 1 Level 3 Min: 1 Def: 1 Max: 3
SED2 VFD Parameter Reference Guide 106 Siemens Building Technologies, Inc. P2221[2] BI: Fixed PID setpoint select Bit 1 Level 3 Min: 0:0 Def: 0:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 107 r2224 CO: Actual fixed PID setpoint Level 3 Min: - Def: - Max: - Un
SED2 VFD Parameter Reference Guide 108 Siemens Building Technologies, Inc. P2228[2] BI: Fixed PID setpoint select Bit 5 Level 3 Min: 0:0 Def: 72
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 109 P2240 Setpoint of PID-MOP Level 3 Min: -200.00 Def: 10.00 Max: 200.0
SED2 VFD Parameter Reference Guide 110 Siemens Building Technologies, Inc. P2254[2] CI: PID trim source Level 3 Min: 0:0 Def: 0:0 Max: 4000:0 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 111 P2265 PID feedback filter timeconstant Level 3 Min: 0.00 Def: 0.00 M
SED2 VFD Parameter Reference Guide 4 Siemens Building Technologies, Inc. Inverter (VFD) Unit (P0004=2) Parameter Description Unit User Setting Min
SED2 VFD Parameter Reference Guide 112 Siemens Building Technologies, Inc. P2271 PID transducer type Level 3 Min: 0 Def: 0 Max: 1 Unit:- Detail
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 113 P2279 PID Neutral Zone Level 3 Min: 0.00 Def: 0.00 Max: 100.00 U
SED2 VFD Parameter Reference Guide 114 Siemens Building Technologies, Inc. P2291 PID output upper limit Level 2 Min: 0.00 Def: 100.00 Max: 100.0
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 115 P2303[2] CI: PID output offset Level 2 Min: 0.0 Def: 0.0 Max: 4000.0
SED2 VFD Parameter Reference Guide 116 Siemens Building Technologies, Inc. P2370 Motor staging stop mode Level 3 Min: 0 Def: 0 Max: 1 Unit: - D
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 117 The following text uses these terms: MV - Variable speed (SED2 controll
SED2 VFD Parameter Reference Guide 118 Siemens Building Technologies, Inc. P2374 Motor staging delay Level 3 Min: 0 Def: 30 Max: 650 Unit: s De
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 119 r2379 CO/BO: Status of motor staging Level 3 Min: - Def: - Max: - U
SED2 VFD Parameter Reference Guide 120 Siemens Building Technologies, Inc. P2390 Hibernation setpoint Level 3 Min: -200.00 Def: 0 Max: 200.00 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 121 P2392 Restart PID error Level 3 Min: -200.00 Def: 0.00 Max: 200.00
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 5 P030
SED2 VFD Parameter Reference Guide Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 Tel: +1 847-2
SED2 VFD Parameter Reference Guide Parameter Description Unit User Setting Min Default Max Access Level 6 Siemens Building Technologies, Inc. P070
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 7 P222
SED2 VFD Parameter Reference Guide Parameter Description Unit User Setting Min Default Max Access Level 8 Siemens Building Technologies, Inc. r077
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 9 P101
SED2 VFD Parameter Reference Guide Parameter Description Unit User Setting Min Default Max Access Level 10 Siemens Building Technologies, Inc. P00
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 11 r00
SED2 VFD Parameter Reference Guide 12 Siemens Building Technologies, Inc. Parameter Description Unit User Setting Min Default Max Access Level r20
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 13 P219
SED2 VFD Parameter Reference Guide Parameter Description Unit User Setting Min Default Max Access Level 14 Siemens Building Technologies, Inc. P22
P0004 Parameter Filters/Categories Parameter Description Unit User Setting Min Default Max Access Level Siemens Building Technologies, Inc. 15 P23
SED2 VFD Parameter Reference Guide 16 Siemens Building Technologies, Inc. Parameter Details (Numeric Listing) r0000 Drive display Level 1 Min: -
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 17 P0004 Parameter filter Level 1 Min: 0 Def: 0 Max: 22 Unit: - Details:
SED2 VFD Parameter Reference Guide 18 Siemens Building Technologies, Inc. P0006 Display mode Level 3 Min: 0 Def: 2 Max: 4 Unit: - Details: Defin
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 19 P0011 Lock for user-defined parameter Level 3 Min: 0 Def: 0 Max: 65535
SED2 VFD Parameter Reference Guide 20 Siemens Building Technologies, Inc. Dependency: First, set P0011 ("lock") to a different value than
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 21 r0020 CO: Actual frequency setpoint Level 3 Min: - Def: - Max: - Unit
SED2 Variable Frequency Drives Parameter Reference Guide
SED2 VFD Parameter Reference Guide 22 Siemens Building Technologies, Inc. r0027 CO: Actual output current Level 3 Min: - Def: - Max: - Unit: A D
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 23 P0040 Reset energy consumption meter Level 3 Min: 0 Def: 0 Max: 1 Uni
SED2 VFD Parameter Reference Guide 24 Siemens Building Technologies, Inc. r0053 CO/BO: Actual status word 2 Level 3 Min: - Def: - Max: - Unit: -
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 25 r0055 CO/BO: Additional Actual control word Level 3 Min: - Def: - Max:
SED2 VFD Parameter Reference Guide 26 Siemens Building Technologies, Inc. r0086 CO: Actual active current Level 3 Min: - Def: - Max: - Unit: A D
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 27 r0200 Actual power stack code number Level 3 Min: - Def: - Max: - Uni
SED2 VFD Parameter Reference Guide 28 Siemens Building Technologies, Inc. P0304 Rated motor voltage Level 1 Min: 10 Def: Varies Max: 2000 Unit:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 29 P0307 Rated motor power Level 1 Min: 0.01 Def: Varies Max: 2000.00 U
SED2 VFD Parameter Reference Guide 30 Siemens Building Technologies, Inc. P0311 Rated motor speed Level 1 Min: 0 Def: Varies Max: 40000 Unit: 1
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 31 P0350 Stator resistance (line-to-line) Level 3 Min: 0.00001 Def: Varie
SED2 VFD Parameter Reference Guide 32 Siemens Building Technologies, Inc. P0501[2] Type of Sensor Level 2 Min: 0 Def: 0 Max: 29 Unit: - Detail
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 33 P0507[3] Scalar Values Level 3 Min: 0 Def: 1.0 Max: 9999.9 Unit: - D
SED2 VFD Parameter Reference Guide 34 Siemens Building Technologies, Inc. P0601 Motor temperature sensor Level 3 Min: 0 Def: 0 Max: 2 Unit: - D
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 35 P0700[2] Selection of command source Level 1 Min: 0 Def: [0] 2 Max: 6
SED2 VFD Parameter Reference Guide 36 Siemens Building Technologies, Inc. P0702[2] Function of digital input 2 Level 2 Min: 0 Def: [0] 12 Max: 9
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 37 P0703[2] Function of digital input 3 Level 2 Min: 0 Def: 9 Max: 99 U
SED2 VFD Parameter Reference Guide 38 Siemens Building Technologies, Inc. P0704[2] Function of digital input 4 Level 2 Min: 0 Def: 15 Max: 99 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 39 P0705[2] Function of digital input 5 Level 2 Min: 0 Def: 15 Max: 99
SED2 VFD Parameter Reference Guide 40 Siemens Building Technologies, Inc. P0706[2] Function of digital input 6 Level 2 Min: 0 Def: 15 Max: 99 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 41 P0707[2] Function of digital input 7 Level 3 Min: 0 Def: 0 Max: 99 U
NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Bu
SED2 VFD Parameter Reference Guide 42 Siemens Building Technologies, Inc. P0708[2] Function of digital input 8 Level 3 Min: 0 Def: 0 Max: 99 Un
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 43 r0722 CO/BO: Binary input values Level 3 Min: - Def: - Max: - Unit:
SED2 VFD Parameter Reference Guide 44 Siemens Building Technologies, Inc. P0731[2] BI: Function of digital output 1 Level 2 Min: 0:0 Def: 52:3 M
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 45 P0732[2] BI: Function of digital output 2 Level 2 Min: 0:0 Def: 52:2
SED2 VFD Parameter Reference Guide 46 Siemens Building Technologies, Inc. r0747 CO/BO: State of digital outputs Level 3 Min: - Def: - Max: - Un
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 47 r0754[2] Actual AI value after scaling, % Level 2 Min: - Def: - Max: -
SED2 VFD Parameter Reference Guide 48 Siemens Building Technologies, Inc. P0756[2] Type of analog input Level 2 Min: 0 Def: 0 Max: 5 Unit: - De
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 49 P0757[2] Value x1 of AI scaling, V/mA Level 2 Min: -50.0 Def: - Max:
SED2 VFD Parameter Reference Guide 50 Siemens Building Technologies, Inc. P0759[2] Value x2 of AI scaling, V/mA Level 2 Min: -50.0 Def: 10 Max:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 51 Example of analog input value 0V to 10V (-50 Hz to +50 Hz) with center ze
SED2 VFD Parameter Reference Guide 52 Siemens Building Technologies, Inc. P0773[2] Smooth time analog output Level 3 Min: 0 Def: 100 Max: 1000
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 53 P0777[2] Value x1 of analog output scaling Level 2 Min: -99999.9 Def:
SED2 VFD Parameter Reference Guide 54 Siemens Building Technologies, Inc. P0779[2] Value x2 of analog output scaling Level 2 Min: -99999.9 Def:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 55 P0810 BI: CDS bit 0 (Local/Remote) Level 3 Min: 0:0 Def: 718:0 Max: 4
SED2 VFD Parameter Reference Guide 56 Siemens Building Technologies, Inc. r0947[8] Last fault code Level 3 Min: - Def: - Max: - Unit: - Details
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 57 Example: If the SED2 trips on undervoltage and then receives an external
SED2 VFD Parameter Reference Guide 58 Siemens Building Technologies, Inc. r0949[8] Fault value Level 3 Min: - Def: - Max: - Unit: - Details: Di
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 59 r0968 Status word 1 Level 3 Min: - Def: - Max: - Unit: - Details: Di
SED2 VFD Parameter Reference Guide 60 Siemens Building Technologies, Inc. P0971 Transfer data from RAM to EEPROM Level 3 Min: 0 Def: 0 Max: 1 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 61 26 CB on COM link + Analog setpoint 27 Analog setpoint 2 + Analog setp
Table of Contents Siemens Building Technologies, Inc. i Table of Contents Overview ...
SED2 VFD Parameter Reference Guide 62 Siemens Building Technologies, Inc. P1001 Fixed frequency 1 Level 3 Min: -650.00 Def: 0.00 Max: 650.00 Uni
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 63 Dependency: Select fixed frequency operation (using P1000). SED2 requir
SED2 VFD Parameter Reference Guide 64 Siemens Building Technologies, Inc. P1006 Fixed frequency 6 Level 3 Min: -650.00 Def: 25.00 Max: 650.00 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 65 P1011 Fixed frequency 11 Level 3 Min: -650.00 Def: 50.00 Max: 650.00
SED2 VFD Parameter Reference Guide 66 Siemens Building Technologies, Inc. P1016 Fixed frequency mode - Bit 0 Level 3 Min: 1 Def: 1 Max: 3 Unit:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 67 P1019 Fixed frequency mode - Bit 3 Level 3 Min: 1 Def: 1 Max: 3 Unit
SED2 VFD Parameter Reference Guide 68 Siemens Building Technologies, Inc. P1022[2] BI: Fixed frequency selection Bit 2 Level 3 Min: 0:0 Def: 0:0
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 69 P1026[2] BI: Fixed frequency selection Bit 4 Level 3 Min: 0:0 Def: 72
SED2 VFD Parameter Reference Guide 70 Siemens Building Technologies, Inc. P1032 Inhibit reverse direction of MOP Level 3 Min: 0 Def: 1 Max: 1 U
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 71 P1080 Min. frequency Level 1 Min: 0.00 Def: 10.00 Max: 650.00 Unit:
SED2 VFD Parameter Reference Guide 72 Siemens Building Technologies, Inc. P1092 Skip frequency 2 Level 3 Min: 0.00 Def: 0.00 Max: 650.00 Unit:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 73 P1110[2] BI: Inhibit negative frequency setpoint Level 3 Min: 0:0 Def
SED2 VFD Parameter Reference Guide 74 Siemens Building Technologies, Inc. P1121 Ramp-down time Level 1 Min: 10.00 Def: 30.00 Max: 650.00 Unit:
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 75 P1142[2] BI: RFG enable setpoint Level 3 Min: 0:0 Def: 1:0 Max: 4000:
SED2 VFD Parameter Reference Guide 76 Siemens Building Technologies, Inc. P1203 Search rate: Flying start Level 3 Min: 10 Def: 100 Max: 200 Uni
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 77 P1211 Number of restart attempts Level 3 Min: 0 Def: 3 Max: 10 Unit:
SED2 VFD Parameter Reference Guide 78 Siemens Building Technologies, Inc. P1230[2] BI: Enable DC braking Level 3 Min: 0:0 Def: 0:0 Max: 4000:0
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 79 P1233 Duration of DC braking Level 3 Min: 0 Def: 0 Max: 250 Unit: s
SED2 VFD Parameter Reference Guide 80 Siemens Building Technologies, Inc. P1260 Reserved Level 2 Min: Def: Max: Unit: r1261 Reserved Leve
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 81 P1300 Control mode Level 3 Min: 0 Def: 2 Max: 23 Unit: - Details: Co
Overview Siemens Building Technologies, Inc. 1 Overview The SED2 uses parameters to define the required operating characteristics, such as motor dat
SED2 VFD Parameter Reference Guide 82 Siemens Building Technologies, Inc. P1310 Continuous boost Level 3 Min: 0.0 Def: 50.0 Max: 250.0 Unit: %
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 83 P1311 Acceleration boost Level 3 Min: 0.0 Def: 0.0 Max: 250.00 Unit:
SED2 VFD Parameter Reference Guide 84 Siemens Building Technologies, Inc. P1312 Starting boost Level 3 Min: 0.0 Def: 0.0 Max: 250.00 Unit: % De
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 85 P1336 Slip limit Level 3 Min: 0 Def: 250 Max: 600 Unit: % Details: C
SED2 VFD Parameter Reference Guide 86 Siemens Building Technologies, Inc. P1820 Reverse output phase sequence Level 3 Min: 0 Def: 0 Max: 1 Unit
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 87 r1912[3] Identified stator resistance Level 3 Min: - Def: - Max: - U
SED2 VFD Parameter Reference Guide 88 Siemens Building Technologies, Inc. P2009[2] USS normalization Level 3 Min: 0 Def: 0 Max: 1 Unit: - Detai
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 89 P2014[2] USS telegram off time Level 3 Min: 0 Def: 0 Max: 65535 Unit
SED2 VFD Parameter Reference Guide 90 Siemens Building Technologies, Inc. P2051[8] CI: PZD to CB Level 3 Min: 0:0 Def: 52:0 Max: 4000:0 Unit: -
Parameter Details (Numeric Listing) Siemens Building Technologies, Inc. 91 r2054[7] CB diagnosis Level 3 Min: - Def: - Max: - Unit: - Details: