18
I-T-E Rear Connecting Studs
General Description
One complete rear stud assembly requires the following:
1 1-12 threaded stud 1 “T” connector
1 Molded stand-off insulator 2 Brass locknuts
1 Insulator bushing 1 5/16-18 X 1 in. mtg. bolt
1 Insulator (req’d for metallic 1 5/16 in. Belleville washer
mtg. panels only
Application Information
Ampere
Rating (In)
Poles Quantity per Breaker
200, 300
400
2 4 of RS-5774
3 4 of RS-5774 plus 2 of RS-5773
500, 600 2 4 of RS-5784
3 4 of RS-5784 plus 2 RS-5783
Mounting Preparation (Figure 1)
A. Drilling locations are shown in Figure 1. The 5/6 in. wide
cutout between holes is required when mounting the
breaker with stud assemblies to a metallic panel.
Breaker Preparation (Figure 2)
A. Remove wire connectors from breaker if present.
B. Attach long and short studs (1), (2) to circuit breaker for
three pole devices, short studs (1) only for two pole
devices. Attach with the 5/,6-18 X 1 in. hex head bolt and
the 5/16 in. serrated cone lockwasher (4). Tighten finger
tight only.
C. Slide one stand-off insulator (5) onto each stud until the
stand-off insulator fully covers the square end of the
studs. Tighten hex head bolt (3) to 132 in. Ib. and install
insulator (10) over studs only if using a metallic mounting
panel.
Final Assembly (Figure 3)
A. Install circuit breaker so that all studs extend through
mounting panel and the stand-off insulators (5) are
seated against the mounting panel.
B. Install insulator bushings (6 and 7) over studs where
required and tighten them securely in place against the
mounting panel with the locknut (8).
C. Thread the second locknut (8) and the “T” connector (9)
over the studs as far as possible where required. Position “T”
connector as desired by loosening (one full turn max.) and
lock in place with the second locknut at 132 in. Ib.
Important User Note
Assemblies are designed with adequate 600 volt electrical
clearance between components. User installation must main-
tain these clearances through spacing or proper insulation.
A. Insert the upper end shields (11) into the slots provided
at the line and load ends of the breaker (Figure 2), one
for each stud position.
B. Affix the label Pc. No. 60229 to breaker cover (Figure 2).
C. Make desired bus bar connections with 5/16 in. bolts
and washers to “T” connectors. (See Figure 3 for hole
pattern of “T” connector).