45
I-T-E JD and LD-Frame
Neutral Sensing Transformer
General
A. Turn off power feeding this device before starting the
installation.
B. Also turn off any line power within the immediate vicinity to
prevent the incidental or accidental contact of tools by
the installer.
NOTE: This instruction sheet outlines the recommended
installation procedure for the following Neutral Sensing
Transformers:
Transformer
Cat. No.
Ampere Rating Color
NO2SJD
NO3SJD
NO4SJD
NO5SLD
NO6SLD
200 Amps
300 Amps
400 Amps
500 Amps
600 Amps
Green
Green
Green
Green
Green
Caution: Incorrect usage of the neutral sensor transformer
could cause nuisance tripping or improper operation of the
ground fault function. Use only the above series of neutral
sensors.
Introduction
This neutral sensing transformer is designed to be mounted
on one 3.00" x .50" bus bar or, two 500 MCM cables,
maximum.
Mounting Procedure
A. Position the neutral sensor within easy wiring range of the
associated circuit breaker and fabricate two .312 diam-
eter holes 2.25 inches apart in bus or panel, as shown in
Figure 1. Orient L-Mounting brackets as necessary for
the mounting configuration being used and secure to the
neutral sensor with the hardware provided.
B. Mount the neutral sensor to bus or panel with 1/4-20
hardware (not provided).
NOTE: The SJD and SLD series of electronic trip circuit
breakers equipped with ground fault protection may be
used in the residual or ground return modes. When used
in the residual mode the orientation of the neutral sensing
transformer is important for proper operation. See Fig-
ures 2 and 3 for proper orientation of the neutral sensor
for residual mode ground fault. Orientation of the neutral
sensor is not required when used in the ground return
mode of ground fault. See Figure 4 for installation of
neutral sensor.