http://www2.merrick-inc.com/mct/GCMModbus.pdf Page 3 2014-05-18/Lars
Parameter
Comment
C: LnPar
UART Line parameter settings, hexadecimal. Bit encoded:
Bit 0, 1 Word Length 00: 5 bits, 01: 6 bits, 10: 7 bits, 11: 8 bits.
Bit 2 Stop bits. 0: 1 stop bit, 1: 2 stop bits
Bit 3 Parity Enable
Bit 4, 5 Parity Select 00: Odd, 01: Even, 10: Forced 1, 11: Forced 0
Bit 6 Enable Break transmission. Always 0!
Bit 7 DLAB Access. Always 0!
Typical settings are 0x03 for N, 8, 1 (most commonly used) and 0x1B for E,8,1
(Modbus RTU default)
E1:WProt
Write Protection bits, hexadecimal. Normally 0xBFF, meaning all tags except the
Primary Setpoint are write protected. See CIT documentation.
E2:Worder
Word Order bits, Hexadecimal. Normally 0x0000, meaning all tags have normal
word order. This has to be found by trial and error. The Siemens S7 PLC, for
example, has the word order for a floating point value reversed (as compared with
a Modicon PLC), so you must enter 0x0FFF. See CIT documentation.
E3:IntFra
Integer/Fraction bits, hexadecimal. Normally 0x0000, meaning all tags are
transferred as Floating Point numbers. See CIT documentation.
Fn:Tag n,
n=1..5
Tagged register number. Up to five internal GCM Register Numbers you want to
monitor or set. The corresponding register value will appear in the "Tag 1 Rd V"
position in the CIT. Register numbers are available in the GCM Firmware
Overview.
G1: Unit
Addr
Modbus “Node Number” Must be different for all slaves on the multidrop serial
line.
G2: Map
Size
There are two different CIT layouts. This document covers CIT type 1 only. Always
set to 1!
G3: Max
Time
Max allowed time between incoming, valid Modbus telegrams addressing the Unit
Address of this GCM. If this time is exhausted, the logical output Port 1 Timeout
or Port 2 Timeout goes on, depending on which port is used for Modbus
communications.
If you extend the size of the write table beyond word 59, you will overwrite “Write Protect”, “Word
Order”, “Int/Frac FP” and "Tag Reg 1-5" parameters from the PLC. This allows for multiplexing of
the parameters in the "Tag n Rd V" positions.
Configuring warnings and faults
Warnings and Faults are qualifiers to logical inputs and outputs, normally set by the user. See
Digital I/O mapping” in the Operations and Maintenance manual. Warnings are considered to
require attention. Faults are considered to be fatal for the feeder operation, and the controller will
attempt to stop the feeder. In this example the warnings and faults are set up according to the
following table:
I/O point
Qualifier
Comment
LoadCell 1 Ovl
Fault
Invalid Load Cell Signal
LoadCell 1 Undl
Fault
Invalid Load Cell Signal
Blt Drive Fail
Fault
Time delayed indication that the belt drive has failed or is not
ready.
High Belt Load
Warning
Too much material on the belt
Belt Drv Ovld
Warning
Signal from the belt motor drive, connected to an MC³