Siemens ITE Spezifikationen Seite 28

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 56
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 27
I-T-E Internal Accessories
C. Slide accessory down to rest on pad (6) trip unit. When
accessory is installed correctly, front of accessory (7) will
rest on pad (8) of line cover. Pull gently and evenly on
accessory wire leads (2 to 6 wires) while lowering
accessory into base. Make sure all the slack is removed
from leads inside breaker.
D. Replace load end cover (3), cover screws (2) and four
mounting screws if mounted. Replace terminal shield
with screws (1).
E. Add two labels to circuit breaker. Attach identification
label (11) to appropriate space in label on top of circuit
breaker on right hand side. Attach accessory informa-
tion label (12) on side of circuit breaker base (Figure 5).
F. Refer to Electrical Check, pages 27 and 28.
Recommended Combinations
Maximum Installable Accessory Combinations
Shunt
Trip(1)
Undervoltag
Trip
Auxiliary
Switch
Bell Alarm
Switch
1 0 1 0
0 1 2 0
0 0 2 0
0 0 2 1
(1) Shunt trip units include a coil clearing switch.
NOTE: See page 51 for catalog combinations.
Figure 4
Figure 5
26
Seitenansicht 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 55 56

Kommentare zu diesen Handbüchern

Keine Kommentare