Command Interface
5-41
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
12 0 Parameter slave 12B Parameter slave 13B
12 1 Parameter slave 14B Parameter slave 15B
12 2 Parameter slave 16B Parameter slave 17B
12 3 Parameter slave 18B Parameter slave 19B
12 4 Parameter slave 20B Parameter slave 21B
12 5 Parameter slave 22B Parameter slave 23B
12 6 Parameter slave 24B Parameter slave 25B
12 7 Parameter slave 26B Parameter slave 27B
12 8 Parameter slave 28B Parameter slave 29B
12 9 Parameter slave 30B Parameter slave 31B
12 10 Flag 1
12 11 Flag 2
Flag 1 Flag 2
Bit Number Meaning
Bit Number Meaning
0 OFFLINE_READY 0 OFFLINE
1 APF 1 INTERNAL
2 NORMAL_MODE 2 EEPROM_OK
3 CONFIG_MODE 3 AUTO_ADDR_ENABLE
4 AUTO_ADDR_AVAIL 4 PERIPHERY_FAULT
5 AUTO_ADDR_ASSI_GN 5 reserved
6 LDS_0 6 reserved
7 CONFIG_OK 7 MPO startup
Flags whose values modify the AS-i master mode are shown on a gray
background.
The values of the other flags have no significance for the ’store total configuration’
command and cannot be modified on the AS-i master with this call.
Only the gray shaded flags can be modified.
CONFIG_MODE The entry ‘0’ means that the CP 243-2 changes to the protected mode after
executing the command. The entry ‘1’ means that the CP continues in the
configuration mode.
0 The AS-i master starts up in the protected mode
on completion of the job.
1 The AS-i master starts up in the configuration mode
on completion of the job.
AUTO_ADDR_ENABLE ’0’ means that the automatic address programming is disabled, ’1’ means
that the automatic address programming is enabled.
0 Automatic address programming disabled.
1 Address programming enabled.