SED2 VFD Startup, Operation, and Maintenance Manual
76 Siemens Building Technologies, Inc.
Network Communications
Table 8 lists the parameters required for correct APOGEE™ system FLN
communications and control of the SED2.
CAUTION:
Changes made to the parameters other than what is listed in
Table 8 can result in damaging the drive or building equipment.
Table 8. Parameters for Network Communications.
Parameter Value
P0003:
User access
Level
Set to 3 to allow access to required parameters.
P2040:
CB telegram
off time
Set to 0 (watchdog disabled) to tell the SED2 to start looking
for communication via the setting of P2041.
P2041[0]:
CB parameter
Set to 1 for FLN (P1) control.
(Set to 2 for FLN (N2) control.)
P0918:
CB address
Set to 99 for (P1) addressing of the device.
(Set to 3 for (N2) addressing of the device.)
Unit must be powered down to establish P1 communications,
and then the address is assigned.
The address will return to the default of 99 when the drive is
powered down.
P0700[0]
Set to 6 tells the SED2 to look for a start command from the
network in the auto mode.
P1000[0]
Set to 6 tells the SED2 to look for its speed source from the
network in the auto mode.
Since there is a limited life to EEPROM writes, set the Network Fault
Indicator to 0 only when troubleshooting a communications problem.
If a factory reset of parameters is desired, set P0010 to 30 and then set
P0970 to 1.
Appendix B: SED2 Point Maps provides a SED2 P1 point map for
APOGEE
®
Automation Systems and a SED2 N2 point map for Johnson
Controls, Inc. systems.