Siemens SIMATIC TI505 Spezifikationen Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 22
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
Simatic/TI 505 Serial Driver Help
Bit 13, 1 = Attempt to invoke restricted special
function program or subroutine.
STW00163 Contains the number of the ladder subroutine that
caused the stack overflow.
x x x x
STW00164-00165 Contains the source RLL checksum (32 Bit
integer).
x x x x
STW00166-00167 Contains the compiled RLL checksum (32 Bit
integer).
x x x x
STW00168 Dual RBC Status.
Bit 1-16 are bases 15-0.
For each Bit:
0 = Dual RBC present and good.
1 = Error or single RBC.
x x x x
STW00169-00175 Not used. x x x x
'STW00176 Dual Power Supply Status.
Bit 1-16 are bases 15-0.
For each Bit:
0 = Dual power supply present and good.
1 = Error or single power supply.
x x x x
STW00177-00183 Not used. x x x x
STW00184 Module Mismatch Indicator.
Bit 1, 1 = Module mismatch error.
Bit 5-8 = Indicates the number of the base with
the error.
x x x x
STW00185-00190 Not used. x x x x
STW00191 Serial Port Print Status. N/A, N/A. N/A. x
STW00192 Discrete Execution Scan Time - The time spent on
the last scan.
x x x x
STW00193-199 Not used. x x x x
STW00200 User Program Error Cause (associated with Bit 6
of STW001). Codes are as follows:
0 = No error.
1 = Reference to an application that is not
installed.***
2 = Attempted to unlock a flag that is not held by
an application.***
3 = Mismatched lock/unlock instructions.***
4 = Subroutine nesting level exceeded.
5 = Table overflow.
6 = Attempted to call a non-existent subroutine.
7 = VMEbus access failed due to a bus error.***
8 = Special function program has not been
compiled or does not exist.
9 = Special function program has been disabled.
10= Special function program type is restricted
or cyclic.
11 = Special function program or subroutine is
being edited.
12 = Special function program or subroutine is
being executed by an interrupt task.
13 = User-scheduled fast loop is not configured.
14 = User-scheduled fast loop is disabled.
x x x x
STW00201 First Scan Flags.
Bit 1, 1 = First Run Mode scan or single scan after
compile.
Bit 2, 1 = First Run Mode scan or single scan after
Program Mode.
x x x x