SD74
11
TABLE 2-1 Double-Acting Cylinder Operators
VALVE DESIGN
Valve Action Down to Close Up to Close Down to Close Up to Close
Maximum
Controller Output,
Valve
Closes Opens Opens Closes
For Controller Air
Failure, Valve
Opens Closes Closes Opens
Positioner Mounting Inverted Inverted Normal Normal
TABLE 2-2 Single-Acting Operators
VALVE DESIGN
Actuator Top Top Bottom Bottom
Valve Action Air Closes Air Opens Air Opens Air Closes
Desired Valve Action
Maximum
Controller Output,
Valve
Closes Opens Opens Closes Opens Closes Closes Opens
For Controller Air
Failure, Valve
Opens Closes Closes Opens Closes Opens Opens Closes
For Positioner
Supply Air Failure,
Valve
Opens Opens Closes Closes Closes Closes Opens Opens
Mounting Position Inverted Normal Inverted Normal Normal Inverted Normal Inverted
Port to be
Connected to
Actuator
Valve 2 Valve 1 Valve 2 Valve 1 Valve 2 Valve 1 Valve 2 Valve 1
Port to be Plugged Valve 1 Valve 2 Valve 1 Valve 2 Valve 1 Valve 2 Valve 1 Valve 2