T400 Controller Facilities Manual
667/EB/20200/000 Page i Issue 9
SIEMENS TRAFFIC CONTROLS LIMITED
Sopers Lane
POOLE Dorset.
BH17 7ER
SYSTEM/PROJECT/PRODUCT: T400 CONTROLLER
T400 CONTROLLER
FACILITIES MANUAL
PREPARED: A.Pickering APPROVED: J.P.Burgess
FUNCTION: Senior Engineer FUNCTION: Engineering Manager
SIGNATURE: SIGNATURE:
ISSUE: CHANGE REF.: DATE: APPROVED BY:
1 16/08/89
2 83/15948 15/02/91
3 83/16122 13/06/91
4 83/16700 24/09/92
5 83/16955 18/12/92
6 83/17014 20/01/93
7 83/17147 23/03/93
8 83/18623 22/05/96
9 Jan 1999
Siemens Traffic Controls Limited 1995 All rights reserved.
The information contained herein is the property of Siemens Traffic Controls Limited and is
supplied without liability for errors or omissions and no part may be reproduced, used or
disclosed except as authorized by contract or other written permission. The copyright and the
foregoing restriction on reproduction, use and disclosure extend to all the media in which this
information may be embodied.
(stcl-pub)
Seitenansicht 0
1 2 3 4 5 6 ... 307 308

Inhaltsverzeichnis

Seite 1 - FACILITIES MANUAL

T400 Controller Facilities Manual667/EB/20200/000 Page i Issue 9SIEMENS TRAFFIC CONTROLS LIMITEDSopers LanePOOLE Dorset.BH17 7ERSYSTEM/PROJECT/PRODUCT

Seite 2

T400 Controller Facilities Manual667/EB/20200/000 Page x Issue 916.1.4 SW1, SW2 and SW3 Pushbuttons...

Seite 3

T400 Controller Facilities Manual667/EB/20200/000 Page 9-40 Issue 99.7.2 Manual Step-on Mode Parallel Stage Streaming FacilitiesEach step is allocate

Seite 4

T400 Controller Facilities Manual667/EB/20200/000 Page 9-41 Issue 99.8 SELECTED FIXED TIME, CLF OR V.A. MODEManually selected ‘FT’, ‘CLF’ and ‘VA’ ar

Seite 5

T400 Controller Facilities Manual667/EB/20200/000 Page 9-42 Issue 9need to be carefully considered, if synchronisation with the rest of the system is

Seite 6

T400 Controller Facilities Manual667/EB/20200/000 Page 9-43 Issue 99.9.1 Example Of Simple Linked InstallationA simple linked installation covering t

Seite 7

T400 Controller Facilities Manual667/EB/20200/000 Page 9-44 Issue 9The group timers in each linking unit are fully synchronous and, provided the total

Seite 8

T400 Controller Facilities Manual667/EB/20200/000 Page 9-45 Issue 99.9.5 Group Influences0. GO TO VA - allows vehicle actuation to operate except tha

Seite 9

T400 Controller Facilities Manual667/EB/20200/000 Page 9-46 Issue 99.9.6 Examples Of PlansSee Figure 21.11.9.9.6(a) Plan 0The sequence will commence

Seite 10

T400 Controller Facilities Manual667/EB/20200/000 Page 9-47 Issue 9The example shown in Figure 9.7(a) would be for a two streamcontroller where Stream

Seite 11

T400 Controller Facilities Manual667/EB/20200/000 Page 9-48 Issue 9b)INFLUENCE SET 2Influence SetCombination ‘A’Influence SetCombination ‘B’GroupInfRe

Seite 12

T400 Controller Facilities Manual667/EB/20200/000 Page 9-49 Issue 9it would be outputting and how many seconds have elapsed within this group if thisp

Seite 13

T400 Controller Facilities Manual667/EB/20200/000 Page xi Issue 917.11.2 Alternative Max. sets...

Seite 14

T400 Controller Facilities Manual667/EB/20200/000 Page 9-50 Issue 9should be specified. If alternatives are specified, it is preferable for thealterna

Seite 15

T400 Controller Facilities Manual667/EB/20200/000 Page 9-51 Issue 9If required (specified by handset command), then every time a grouptime withinthe c

Seite 16

T400 Controller Facilities Manual667/EB/20200/000 Page 9-52 Issue 9Combination ‘A’ would be used for Stream 0, Influence Set Combination ‘B’ forStream

Seite 17 - 1. INTRODUCTION

T400 Controller Facilities Manual667/EB/20200/000 Page 9-53 Issue 99.10 VEHICLE ACTUATED (VA) MODEIn VA mode the controller monitors all demands, ext

Seite 18

T400 Controller Facilities Manual667/EB/20200/000 Page 9-54 Issue 9Figure 9.8 - EXAMPLE OF VA STAGE CHANGES AACEGSTAGE 2DSTAGE 1BSTAGE 3 STAGE 4EFEF‘I

Seite 19

T400 Controller Facilities Manual667/EB/20200/000 Page 9-55 Issue 99.10.2 Arterial Reversion Parallel Stage Streaming FacilitiesThere is an Arterial

Seite 20

T400 Controller Facilities Manual667/EB/20200/000 Page 9-56 Issue 99.11 FIXED TIME WORKINGThere are two methods of obtaining fixed time working:- Fi

Seite 21 - 2. STAGES

T400 Controller Facilities Manual667/EB/20200/000 Page 9-57 Issue 9If Fixed time to current maximum is to be the default/lowest mode of operation. The

Seite 22

T400 Controller Facilities Manual667/EB/20200/000 Page 9-58 Issue 9timer will start when all stages have appeared. This process will be repeated for e

Seite 23

T400 Controller Facilities Manual667/EB/20200/000 Page 9-59 Issue 99.12 MODE PRIORITYThe mode priority facility allows for the mode with the highest p

Seite 24

T400 Controller Facilities Manual667/EB/20200/000 Page xii Issue 921. EXAMPLE OF AN INTERSECTION ...

Seite 25

T400 Controller Facilities Manual667/EB/20200/000 Page 9-60 Issue 9Similarly to select Manual mode the MANUAL mode select button is selected and ifSEL

Seite 26

T400 Controller Facilities Manual667/EB/20200/000 Page 9-61 Issue 99.13 TIMER RELATIONSHIPSBelow is a simple diagram intended to indicate the relatio

Seite 27

T400 Controller Facilities Manual667/EB/20200/000 Page 10-1 Issue 910. STAGE MOVEMENT RESTRICTIONSWhen a specific stage change is required not to occ

Seite 28

T400 Controller Facilities Manual667/EB/20200/000 Page 10-2 Issue 910.1 PROHIBITED MOVESWhen a move to a stage is prohibited and there is a demand fo

Seite 29

T400 Controller Facilities Manual667/EB/20200/000 Page 10-3 Issue 9may be stage change conditions present for Stage 2 and ROW will go there beforeStag

Seite 30 - 3. PHASES

T400 Controller Facilities Manual667/EB/20200/000 Page 10-4 Issue 910.5 PREVENTED STAGES/PHASESThe deletion of a stage or phase, which may be achieved

Seite 31

T400 Controller Facilities Manual667/EB/20200/000 Page 11-1 Issue 911. THE MASTER TIME CLOCK SYSTEM11.1 INTRODUCTIONThe master time clock system (MTC

Seite 32

T400 Controller Facilities Manual667/EB/20200/000 Page 11-2 Issue 9If the mains fails for more than 30 days (this threshold is configurable and alsoal

Seite 33

T400 Controller Facilities Manual667/EB/20200/000 Page 12-1 Issue 912. THE EVENT TIMETABLE12.1 PLAN CHANGE/EVENT TIMETABLEThere are 64 entries in th

Seite 34

T400 Controller Facilities Manual667/EB/20200/000 Page 12-2 Issue 912.2.1 Synchronisation of Cableless Linking EquipmentSynchronisation of Cableless

Seite 35

T400 Controller Facilities Manual667/EB/20200/000 Page xiii Issue 9B.1 50-0-50 volt Controller ...

Seite 36

T400 Controller Facilities Manual667/EB/20200/000 Page 12-3 Issue 9inactive will set it permanently inactive. The state will continue until another ti

Seite 37

T400 Controller Facilities Manual667/EB/20200/000 Page 12-4 Issue 9If a real phase is deleted, then the signals will remain at red (or blackout in the

Seite 38

T400 Controller Facilities Manual667/EB/20200/000 Page 12-5 Issue 912.3.1 Event Switch Default StatesEvent Default StateMaxSwitch Set A and Priority

Seite 39

T400 Controller Facilities Manual667/EB/20200/000 Page 12-6 Issue 9At 12-30 Alternative Maximum Set D is introduced and Dummy Phase I remainsdeleted w

Seite 40

T400 Controller Facilities Manual667/EB/20200/000 Page 13-1 Issue 913. LINKING13.1 PELICAN CONTROLLERA link to an adjacent Pelican Controller may be

Seite 41

T400 Controller Facilities Manual667/EB/20200/000 Page 13-2 Issue 913.2 REPEAT PULSESThe Type 400 Controller may be linked to other traffic controller

Seite 42

T400 Controller Facilities Manual667/EB/20200/000 Page 14-1 Issue 914. ALTERNATIVE SIGNAL SEQUENCES AND FLASHING SIGNALS14.1 ALTERNATIVE SIGNAL SEQU

Seite 43 - 4. DEMANDS AND EXTENSIONS

T400 Controller Facilities Manual667/EB/20200/000 Page 14-2 Issue 9If this sequence is required, the pedestrian phase has to be programmed as a traffi

Seite 44

T400 Controller Facilities Manual667/EB/20200/000 Page 14-3 Issue 914.3 FLASHING SIGNALSThe signals on traffic, pedestrian and green arrow phases are

Seite 45

T400 Controller Facilities Manual667/EB/20200/000 Page 14-4 Issue 914.4 EXPORT SIGNAL SEQUENCESThe following is a list of some of the foreign signal

Seite 46 - 5. CALL/CANCEL

T400 Controller Facilities Manual667/EB/20200/000 Page xiv Issue 9TABLE OF FIGURESFIGURE 6.1 - SDE/SA LAYOUTS ...

Seite 47

T400 Controller Facilities Manual667/EB/20200/000 Page 14-5 Issue 9HONG KONG: Startup sequence:A 7-10 second blackout, followed by all red usually 8 s

Seite 48

T400 Controller Facilities Manual667/EB/20200/000 Page 15-1 Issue 915. INPUTS AND OUTPUTS15.1 INPUTS (I/P)Inputs into the controller may include the

Seite 49

T400 Controller Facilities Manual667/EB/20200/000 Page 15-2 Issue 915.5 PROVISION OF I/O ON EXPANSION I/O, MAIN PROCESSOR AND SDE/SABOARDSThere are 1

Seite 50

T400 Controller Facilities Manual667/EB/20200/000 Page 15-3 Issue 915.6.1 Cable AssembliesA cable assembly consists of a cable with one or two 12-way

Seite 51 - Figure 6.1 - SDE/SA LAYOUTS

T400 Controller Facilities Manual667/EB/20200/000 Page 15-4 Issue 915.7 PORT ALLOCATIONPort numbers are allocated as per the following table:Board Ty

Seite 52 - 7. ALL-RED DISPLAYS

T400 Controller Facilities Manual667/EB/20200/000 Page 15-5 Issue 9Figure 15.1 - BLOCK DIAGRAM OF MAIN PROCESSOR BOARDREARFRONTPOWER ON LED(GREEN)WATC

Seite 53

T400 Controller Facilities Manual667/EB/20200/000 Page 15-6 Issue 9Figure 15.2 - PCB POSITIONS AND LAYOUT OF PHASE DRIVER RIBBONCABLESPHASEDRIVERA-DI/

Seite 54

T400 Controller Facilities Manual667/EB/20200/000 Page 15-7 Issue 9Figure 15.3 - REAR VIEW OF PCB I/O CONNECTIONS (T400 LARGE SHOWN)PHASEDRIVERA-DPHAS

Seite 55

T400 Controller Facilities Manual667/EB/20200/000 Page 15-8 Issue 9Figure 15.4 - TERMINAL BLOCKS IN SMALL CONTROLLERTERMINALBLOCKSPCB MODULE(EXPANSION

Seite 56 - 8. PHASE DELAYS

T400 Controller Facilities Manual667/EB/20200/000 Page 15-9 Issue 9Figure 15.5 - TERMINAL BLOCKS IN LARGE CONTROLLERBB X T R NZDDCC AA Y W S PEELJGECA

Seite 57

T400 Controller Facilities Manual667/EB/20200/000 Page xv Issue 9FIGURE 21.3 - CUSTOMER SPEC SHEET EXAMPLE ... 21-

Seite 58

T400 Controller Facilities Manual667/EB/20200/000 Page 15-10 Issue 9Figure 15.6 - TERMINAL BLOCKS IN LARGE CONTROLLER (HONG KONG)SECOND PANEL (FITTED

Seite 59

T400 Controller Facilities Manual667/EB/20200/000 Page 15-11 Issue 915.8 ‘DET’ HANDSET COMMANDEach bit of each port has an I/O line number which is u

Seite 60

T400 Controller Facilities Manual667/EB/20200/000 Page 15-12 Issue 9An example of this is a stage that is required not to appear initially. The stage

Seite 61 - 9. MODES

T400 Controller Facilities Manual667/EB/20200/000 Page 15-13 Issue 915.9.1 DFM Timing15.9.1(a) Option 1The timing range of the DFM is 0 to 255 hours

Seite 62

T400 Controller Facilities Manual667/EB/20200/000 Page 15-14 Issue 9If the detector is active for greater than 60 minutes.If the detector is inactive

Seite 63

T400 Controller Facilities Manual667/EB/20200/000 Page 16-1 Issue 916. MANUAL PANELSee Figure 16.1.16.1 STANDARD FACILITIES (Intersection Controller)

Seite 64

T400 Controller Facilities Manual667/EB/20200/000 Page 16-2 Issue 916.1.6 DFM Reset Push-button (If Configured)The DFM RESET push-button extinguishes

Seite 65

T400 Controller Facilities Manual667/EB/20200/000 Page 16-3 Issue 9If more than three indicators are required, then the HURRY CALL active or HIGHERPRI

Seite 66

T400 Controller Facilities Manual667/EB/20200/000 Page 16-4 Issue 916.3 PELICAN MANUAL PANELThe Manual Panel used on a Pelican controller is essentia

Seite 67

T400 Controller Facilities Manual667/EB/20200/000 Page 16-5 Issue 9Figure 16.1 - MANUAL PANEL3CABINETALARMALLRED1 24 56 7NORMALMANUAL CONTROLMANUALFIX

Seite 68

T400 Controller Facilities Manual667/EB/20200/000 Page xvi Issue 9FIGURE 22.26 - CUSTOMER SPEC SHEET EXAMPLE ... 22-27

Seite 69

T400 Controller Facilities Manual667/EB/20200/000 Page 16-6 Issue 9Figure 16.2 - INTERNAL MANUAL PANEL (HONG KONG)3ALLRED124567NORMALMANUAL CONTROLMAN

Seite 70

T400 Controller Facilities Manual667/EB/20200/000 Page 17-1 Issue 917. PELICAN/PEDESTRIAN CONTROLLER17.1 GENERALThere are a number of pelican configu

Seite 71

T400 Controller Facilities Manual667/EB/20200/000 Page 17-2 Issue 917.1.2(c) Pre-timed Maximum Vehicle GreenThis is an alternative form of VA mode if

Seite 72

T400 Controller Facilities Manual667/EB/20200/000 Page 17-3 Issue 917.3 MANUAL PANEL FACILITIESA different manual panel is required for the T400 when

Seite 73

T400 Controller Facilities Manual667/EB/20200/000 Page 17-4 Issue 917.4 HANDSETOn street selection of pelican facilities by the handset can be carried

Seite 74

T400 Controller Facilities Manual667/EB/20200/000 Page 17-5 Issue 917.5 I/O LINE ALLOCATIONEach of the following functions may be allocated to an I/O

Seite 75

T400 Controller Facilities Manual667/EB/20200/000 Page 17-6 Issue 917.6 WAIT INDICATORSThis facility allows the user to select (via the handset) whet

Seite 76

T400 Controller Facilities Manual667/EB/20200/000 Page 17-7 Issue 917.10 DESCRIPTION OF I/O LINE FUNCTIONSPelican I/O SummaryControl Bits UTCTitle Bi

Seite 77

T400 Controller Facilities Manual667/EB/20200/000 Page 17-8 Issue 917.10.1 UTC Facilities (Control Bits)UTC Ped. Inhibit (PV)This input signal preven

Seite 78

T400 Controller Facilities Manual667/EB/20200/000 Page 17-9 Issue 9Switch to Alternative TimingsThis input signal forces the Pelican to switch to the

Seite 79

T400 Controller Facilities Manual667/EB/20200/000 Page 1-1 Issue 91. INTRODUCTIONThis manual refers to the facilities available in the Type 400 Contro

Seite 80

T400 Controller Facilities Manual667/EB/20200/000 Page 17-10 Issue 9Signals Off Confirm (LE)This output signal indicates that the signals on the CPU

Seite 81

T400 Controller Facilities Manual667/EB/20200/000 Page 17-11 Issue 9 (i) it will ignore the PV1 signal and revert to normal unlinked operationand on

Seite 82

T400 Controller Facilities Manual667/EB/20200/000 Page 17-12 Issue 9Link Out (Vehicle green confirm)This output signal is essentially a Vehicle Green

Seite 83

T400 Controller Facilities Manual667/EB/20200/000 Page 17-13 Issue 9NOTE: Pedestrian demands from UTC or local link operate as on the Pelicancontrolle

Seite 84

T400 Controller Facilities Manual667/EB/20200/000 Page 17-14 Issue 917.11 TIMESWITCH FACILITIES17.11.1 Switch Audio offThis facility allows the pelic

Seite 85

T400 Controller Facilities Manual667/EB/20200/000 Page 17-15 Issue 917.12.3 Special Detector checking.This facility is used in VA Mode. When enabled

Seite 86

T400 Controller Facilities Manual667/EB/20200/000 Page 17-16 Issue 9Figure 17.1 - Pelican Manual Panel (Standard)CABINETALARMCONT PEDDEMANDCONTVEHICLE

Seite 87

T400 Controller Facilities Manual667/EB/20200/000 Page 17-17 Issue 9Figure 17.2 - Pelican Manual panel (Basic)CABINETALARMOFFSIGNALSON

Seite 88

T400 Controller Facilities Manual667/EB/20200/000 Page 18-1 Issue 918. EQUIPMENT18.1 PHASE FACILITIESThe Intersection Controller can drive up to 16 re

Seite 89

T400 Controller Facilities Manual667/EB/20200/000 Page 18-2 Issue 918.3 PED. AUDIBLE / TACTILE INDICATION (MCE0141 CONTROLLERS ONLY)Items Required:K-

Seite 90

T400 Controller Facilities Manual667/EB/20200/000 Page 1-2 Issue 91.1 GLOSSARY OF TERMSAbbreviationsAC Alternating CurrentCET Cable Earth TerminalCLF

Seite 91

T400 Controller Facilities Manual667/EB/20200/000 Page 18-3 Issue 918.5 DUAL LEVEL AUDIBLESItems Required:Kit Of Parts to add secondary buzzer...

Seite 92

T400 Controller Facilities Manual667/EB/20200/000 Page 18-4 Issue 9DetectorsSiemens (ST) Self Tune Detectors MkII 667/1/17180/012 = 2 detector channel

Seite 93

T400 Controller Facilities Manual667/EB/20200/000 Page 18-5 Issue 9Alternatively, a special conditioning flag can be set from the MTC timetable to ind

Seite 94

T400 Controller Facilities Manual667/EB/20200/000 Page 18-6 Issue 918.12 POWERING EXTERNALLY SITUATED D-DETECTORS WITH PSU TYPE667/1/20654/000Items Re

Seite 95

T400 Controller Facilities Manual667/EB/20200/000 Page 18-7 Issue 9Figure 18.1 - PEDESTRIAN AUDIBLE INDICATION (SIGNAL HEAD MOUNTING)(Note: If it is r

Seite 96

T400 Controller Facilities Manual667/EB/20200/000 Page 18-8 Issue 9Figure 18.2 - PEDESTRIAN AUDIBLE INDICATION (CONTROLLER MOUNTING)(Note: If it is no

Seite 97

T400 Controller Facilities Manual667/EB/20200/000 Page 18-9 Issue 9Figure 18.3 - PEDESTRIAN TACTILE INDICATION (SIGNAL HEAD MOUNTING)(Note: If it is r

Seite 98

T400 Controller Facilities Manual667/EB/20200/000 Page 18-10 Issue 9Figure 18.4 - PEDESTRIAN TACTILE INDICATION (CONTROLLER MOUNTING)(Note: If it is n

Seite 99

T400 Controller Facilities Manual667/EB/20200/000 Page 18-11 Issue 9Figure 18.5 - POSSIBLE PCB CONFIGURATIONSPhaseDriverPhaseDriverPhaseDriverPhaseDri

Seite 100 - DOOR MICROSWITCH

T400 Controller Facilities Manual667/EB/20200/000 Page 18-12 Issue 9Figure 18.6 - FRONT VIEW OF THE TYPE 400 CONTROLLER (LARGE O/C)OTU or OMU (if fitt

Seite 101

T400 Controller Facilities Manual667/EB/20200/000 Page 1-3 Issue 9RLMU Red Lamp Monitor UnitRMS Root Mean SquareROW Right Of WayRTC Real Time ClockSA

Seite 102

T400 Controller Facilities Manual667/EB/20200/000 Page 18-13 Issue 9Figure 18.7 - FRONT VIEW OF THE TYPE 400 CONTROLLER (SMALL O/C)(see Figure 15.4 -

Seite 103

T400 Controller Facilities Manual667/EB/20200/000 Page 18-14 Issue 9Figure 18.8 - CONNECTING DUAL LEVEL AUDIBLESContact protectionresistor(normally 22

Seite 104

T400 Controller Facilities Manual667/EB/20200/000 Page 18-15 Issue 9Figure 18.9 - Single Sided Access T400LTELECOMSCONNECTION POSTSEE 667/GA/20287/250

Seite 105

T400 Controller Facilities Manual667/EB/20200/000 Page 18-16 Issue 9DANGERPHASE PCB(S) LOCATIONUP TO 16 PHASESCPU AND I/O PCB(S) ETCLOCATIONPOLYESTER

Seite 106

T400 Controller Facilities Manual667/EB/20200/000 Page 19-1 Issue 919. ORIGINAL LAMP MONITORING UNITThis is a separate item of hardware and is not pa

Seite 107

T400 Controller Facilities Manual667/EB/20200/000 Page 19-2 Issue 9Figure 19.1 - LAMP MONITOR OVERVIEWCurrent SensorInputsGreen Voltage InputsLamp Sup

Seite 108

T400 Controller Facilities Manual667/EB/20200/000 Page 19-3 Issue 919.1 LAMP MONITOR + OTU (NOT RED LAMP MONITORING)With the standard lamp monitoring

Seite 109

T400 Controller Facilities Manual667/EB/20200/000 Page 19-4 Issue 919.2 RED LAMP MONITORINGThis facility monitors the state of lamps at an intersecti

Seite 110

T400 Controller Facilities Manual667/EB/20200/000 Page 19-5 Issue 9NOTES (1) CLF Mode - When calculating the minimum cycle time of a CLF plan the Rede

Seite 111

T400 Controller Facilities Manual667/EB/20200/000 Page 19-6 Issue 9a) Red Lamp Monitoring on Part-Time SignalsThe LMU outputs have the following effec

Seite 112

T400 Controller Facilities Manual667/EB/20200/000 Page ii Issue 9SAFETY WARNINGIn the interests of health and safety, when using or servicing this equ

Seite 113

T400 Controller Facilities Manual667/EB/20200/000 Page 1-4 Issue 9667/HA/20200/000MAINTENANCE HANDBOOK FOR THE T400 CONTROLLERThis handbook details th

Seite 114

T400 Controller Facilities Manual667/EB/20200/000 Page 19-7 Issue 9 Case 3 - Controller making transition to the Stage whichcontains t

Seite 115

T400 Controller Facilities Manual667/EB/20200/000 Page 19-8 Issue 9Figure 19.3 - LMU Hold without losing phase delayR/AAAMBERAMBERAMBERAMBERABCDR/AR/A

Seite 116

T400 Controller Facilities Manual667/EB/20200/000 Page 19-9 Issue 9Figure 19.4 - LMU Hold with losing phase delayR/AAAMBERAMBERAMBERAMBERABCDR/AR/AR/A

Seite 117

T400 Controller Facilities Manual667/EB/20200/000 Page 19-10 Issue 919.3 L.M.U. PARALLEL STAGE STREAMING FACILITIES19.3.1 LMU Supplementary Intergre

Seite 118

T400 Controller Facilities Manual667/EB/20200/000 Page 19-11 Issue 919.4 SET UP CONNECTIONS FOR RED LAMP MONITORINGInstallation is in accordance with

Seite 119

T400 Controller Facilities Manual667/EB/20200/000 Page 19-12 Issue 919.4.4 Configuration RequirementsStarting Intergreen: A value of 8 seconds is req

Seite 120

T400 Controller Facilities Manual667/EB/20200/000 Page 20-1 Issue 920. SPECIAL CONDITIONING20.1 INTRODUCTIONThere are often special requirements for t

Seite 121

T400 Controller Facilities Manual667/EB/20200/000 Page 20-2 Issue 920.4 READING CONTROLLER TIMERSIt is possible to read whether certain controller ti

Seite 122

T400 Controller Facilities Manual667/EB/20200/000 Page 20-3 Issue 9ExampleIf a side road phase is extending towards its maximum and a demand is insert

Seite 123

T400 Controller Facilities Manual667/EB/20200/000 Page 21-1 Issue 921. EXAMPLE OF AN INTERSECTIONThis section consists of an example of an intersecti

Seite 124

T400 Controller Facilities Manual667/EB/20200/000 Page 2-1 Issue 92. STAGES2.1 FACILITIESThere are up to 16 stages (0 to 15) available for use.Stage 0

Seite 125

T400 Controller Facilities Manual667/EB/20200/000 Page 21-2 Issue 9Figure 21.1 - CUSTOMER SPEC SHEET EXAMPLE

Seite 126

T400 Controller Facilities Manual667/EB/20200/000 Page 21-3 Issue 9Figure 21.2 - CUSTOMER SPEC SHEET EXAMPLE

Seite 127

T400 Controller Facilities Manual667/EB/20200/000 Page 21-4 Issue 9Figure 21.3 - CUSTOMER SPEC SHEET EXAMPLE

Seite 128 - 12. THE EVENT TIMETABLE

T400 Controller Facilities Manual667/EB/20200/000 Page 21-5 Issue 9Figure 21.4 - CUSTOMER SPEC SHEET EXAMPLE

Seite 129

T400 Controller Facilities Manual667/EB/20200/000 Page 21-6 Issue 9Figure 21.4a - CUSTOMER SPEC SHEET EXAMPLE

Seite 130

T400 Controller Facilities Manual667/EB/20200/000 Page 21-7 Issue 9Figure 21.5 - CUSTOMER SPEC SHEET EXAMPLE

Seite 131

T400 Controller Facilities Manual667/EB/20200/000 Page 21-8 Issue 9Figure 21.6a - CUSTOMER SPEC SHEET EXAMPLE

Seite 132

T400 Controller Facilities Manual667/EB/20200/000 Page 21-9 Issue 9Figure 21.6b - CUSTOMER SPEC SHEET EXAMPLE

Seite 133

T400 Controller Facilities Manual667/EB/20200/000 Page 21-10 Issue 9Figure 21.7 - CUSTOMER SPEC SHEET EXAMPLE

Seite 134 - 13. LINKING

T400 Controller Facilities Manual667/EB/20200/000 Page 21-11 Issue 9Figure 21.8 - CUSTOMER SPEC SHEET EXAMPLE

Seite 135

T400 Controller Facilities Manual667/EB/20200/000 Page 2-2 Issue 9Firstly, the controller sets the “suggested stage” as the current stage and the numb

Seite 136

T400 Controller Facilities Manual667/EB/20200/000 Page 21-12 Issue 9Figure 21.8a - CUSTOMER SPEC SHEET EXAMPLE

Seite 137

T400 Controller Facilities Manual667/EB/20200/000 Page 21-13 Issue 9Figure 21.9 - CUSTOMER SPEC SHEET EXAMPLE

Seite 138

T400 Controller Facilities Manual667/EB/20200/000 Page 21-14 Issue 9Figure 21.9a - CUSTOMER SPEC SHEET EXAMPLE

Seite 139

T400 Controller Facilities Manual667/EB/20200/000 Page 21-15 Issue 9Figure 21.9b - CUSTOMER SPEC SHEET EXAMPLE

Seite 140

T400 Controller Facilities Manual667/EB/20200/000 Page 21-16 Issue 9Figure 21.10 - CUSTOMER SPEC SHEET EXAMPLE

Seite 141 - 15. INPUTS AND OUTPUTS

T400 Controller Facilities Manual667/EB/20200/000 Page 21-17 Issue 9Figure 21.11 - CUSTOMER SPEC SHEET EXAMPLE

Seite 142

T400 Controller Facilities Manual667/EB/20200/000 Page 21-18 Issue 9Figure 21.12 - CUSTOMER SPEC SHEET EXAMPLE

Seite 143

T400 Controller Facilities Manual667/EB/20200/000 Page 21-19 Issue 9Figure 21.13 - CUSTOMER SPEC SHEET EXAMPLE

Seite 144

T400 Controller Facilities Manual667/EB/20200/000 Page 21-20 Issue 9Figure 21.14 - CUSTOMER SPEC SHEET EXAMPLE

Seite 145 - REARFRONT

T400 Controller Facilities Manual667/EB/20200/000 Page 21-21 Issue 9Figure 21.15 - CUSTOMER SPEC SHEET EXAMPLE

Seite 146

T400 Controller Facilities Manual667/EB/20200/000 Page 2-3 Issue 9If NO, add the demand phases in this stage (or the stage itself if stage isdemanded)

Seite 147

T400 Controller Facilities Manual667/EB/20200/000 Page 21-22 Issue 9Figure 21.16 - CUSTOMER SPEC SHEET EXAMPLE

Seite 148

T400 Controller Facilities Manual667/EB/20200/000 Page 21-23 Issue 9Figure 21.17 - CUSTOMER SPEC SHEET EXAMPLE

Seite 149 - DISTRIBUTION PANEL

T400 Controller Facilities Manual667/EB/20200/000 Page 21-24 Issue 9Figure 21.18 - CUSTOMER SPEC SHEET EXAMPLE

Seite 150

T400 Controller Facilities Manual667/EB/20200/000 Page 21-25 Issue 9Figure 21.19 - CUSTOMER SPEC SHEET EXAMPLE

Seite 151

T400 Controller Facilities Manual667/EB/20200/000 Page 21-26 Issue 9Figure 21.20 - CUSTOMER SPEC SHEET EXAMPLE

Seite 152

T400 Controller Facilities Manual667/EB/20200/000 Page 21-27 Issue 9Figure 21.21 - CUSTOMER SPEC SHEET EXAMPLE

Seite 153

T400 Controller Facilities Manual667/EB/20200/000 Page 22-1 Issue 922. EXAMPLE OF AN INTERSECTION ROAD TRAFFIC & LIGHT RAILVEHICLESThis section c

Seite 154

T400 Controller Facilities Manual667/EB/20200/000 Page 22-2 Issue 9Figure 22.1 - CUSTOMER SPEC SHEET EXAMPLE

Seite 155 - 16. MANUAL PANEL

T400 Controller Facilities Manual667/EB/20200/000 Page 22-3 Issue 9Figure 22.2 - CUSTOMER SPEC SHEET EXAMPLE

Seite 156

T400 Controller Facilities Manual667/EB/20200/000 Page 22-4 Issue 9Figure 22.3 - CUSTOMER SPEC SHEET EXAMPLE

Seite 157

T400 Controller Facilities Manual667/EB/20200/000 Page 2-4 Issue 9However, in other modes, namely CLF, UTC, Fixed Time, Priority, Part-Time, Manualand

Seite 158

T400 Controller Facilities Manual667/EB/20200/000 Page 22-5 Issue 9Figure 22.4 - CUSTOMER SPEC SHEET EXAMPLE

Seite 159

T400 Controller Facilities Manual667/EB/20200/000 Page 22-6 Issue 9Figure 22.5 - CUSTOMER SPEC SHEET EXAMPLE

Seite 160 - MANUAL CONTROL

T400 Controller Facilities Manual667/EB/20200/000 Page 22-7 Issue 9Figure 22.6 - CUSTOMER SPEC SHEET EXAMPLE

Seite 161

T400 Controller Facilities Manual667/EB/20200/000 Page 22-8 Issue 9Figure 22.7 - CUSTOMER SPEC SHEET EXAMPLE

Seite 162

T400 Controller Facilities Manual667/EB/20200/000 Page 22-9 Issue 9Figure 22.8 - CUSTOMER SPEC SHEET EXAMPLE

Seite 163

T400 Controller Facilities Manual667/EB/20200/000 Page 22-10 Issue 9Figure 22.9 - CUSTOMER SPEC SHEET EXAMPLE

Seite 164

T400 Controller Facilities Manual667/EB/20200/000 Page 22-11 Issue 9Figure 22.10 - CUSTOMER SPEC SHEET EXAMPLE

Seite 165

T400 Controller Facilities Manual667/EB/20200/000 Page 22-12 Issue 9Figure 22.11 - CUSTOMER SPEC SHEET EXAMPLE

Seite 166

T400 Controller Facilities Manual667/EB/20200/000 Page 22-13 Issue 9Figure 22.12 - CUSTOMER SPEC SHEET EXAMPLE

Seite 167

T400 Controller Facilities Manual667/EB/20200/000 Page 22-14 Issue 9Figure 22.13 - CUSTOMER SPEC SHEET EXAMPLE

Seite 168

T400 Controller Facilities Manual667/EB/20200/000 Page 2-5 Issue 9All stages contained within a stream must be numbered consecutively starting at Stag

Seite 169

T400 Controller Facilities Manual667/EB/20200/000 Page 22-15 Issue 9Figure 22.14 - CUSTOMER SPEC SHEET EXAMPLE

Seite 170

T400 Controller Facilities Manual667/EB/20200/000 Page 22-16 Issue 9Figure 22.15 - CUSTOMER SPEC SHEET EXAMPLE

Seite 171

T400 Controller Facilities Manual667/EB/20200/000 Page 22-17 Issue 9Figure 22.16 - CUSTOMER SPEC SHEET EXAMPLE

Seite 172

T400 Controller Facilities Manual667/EB/20200/000 Page 22-18 Issue 9Figure 22.17 - CUSTOMER SPEC SHEET EXAMPLE

Seite 173

T400 Controller Facilities Manual667/EB/20200/000 Page 22-19 Issue 9Figure 22.18 - CUSTOMER SPEC SHEET EXAMPLE

Seite 174

T400 Controller Facilities Manual667/EB/20200/000 Page 22-20 Issue 9Figure 22.19 - CUSTOMER SPEC SHEET EXAMPLE

Seite 175

T400 Controller Facilities Manual667/EB/20200/000 Page 22-21 Issue 9Figure 22.20 - CUSTOMER SPEC SHEET EXAMPLE

Seite 176

T400 Controller Facilities Manual667/EB/20200/000 Page 22-22 Issue 9Figure 22.21 - CUSTOMER SPEC SHEET EXAMPLE

Seite 177

T400 Controller Facilities Manual667/EB/20200/000 Page 22-23 Issue 9Figure 22.22 - CUSTOMER SPEC SHEET EXAMPLE

Seite 178 - 18. EQUIPMENT

T400 Controller Facilities Manual667/EB/20200/000 Page 22-24 Issue 9Figure 22.23 - CUSTOMER SPEC SHEET EXAMPLE

Seite 179

T400 Controller Facilities Manual667/EB/20200/000 Page 2-6 Issue 92.6.4 Mode Operation(See also section 9.)2.6.4(a) Fixed TimeEach stream will have

Seite 180

T400 Controller Facilities Manual667/EB/20200/000 Page 22-25 Issue 9Figure 22.24 - CUSTOMER SPEC SHEET EXAMPLE

Seite 181

T400 Controller Facilities Manual667/EB/20200/000 Page 22-26 Issue 9Figure 22.25 - CUSTOMER SPEC SHEET EXAMPLE

Seite 182

T400 Controller Facilities Manual667/EB/20200/000 Page 22-27 Issue 9Figure 22.26 - CUSTOMER SPEC SHEET EXAMPLE

Seite 183

T400 Controller Facilities Manual667/EB/20200/000 Page 22-28 Issue 9Figure 22.27 - CUSTOMER SPEC SHEET EXAMPLE

Seite 184 - Pedestrian Signal Head

T400 Controller Facilities Manual667/EB/20200/000 Page 22-29 Issue 9Figure 22.28 - CUSTOMER SPEC SHEET EXAMPLE

Seite 185 - Controller

T400 Controller Facilities Manual667/EB/20200/000 Page 22-30 Issue 9Figure 22.29 - CUSTOMER SPEC SHEET EXAMPLE

Seite 186 - MCE0125 Pelican Signal Head

T400 Controller Facilities Manual667/EB/20200/000 Page 22-31 Issue 9Figure 22.30 - CUSTOMER SPEC SHEET EXAMPLE

Seite 187 - Signal Head

T400 Controller Facilities Manual667/EB/20200/000 Page 22-32 Issue 9Figure 22.31 - CUSTOMER SPEC SHEET EXAMPLE

Seite 188

T400 Controller Facilities Manual667/EB/20200/000 Page 22-33 Issue 9Figure 22.32 - CUSTOMER SPEC SHEET EXAMPLE

Seite 189

T400 Controller Facilities Manual667/EB/20200/000 Page 23-1 Issue 923. MOVA (MICROPROCESSOR OPTIMISED VEHICLE ACTUATION)At present, MOVA is implement

Seite 190

T400 Controller Facilities Manual667/EB/20200/000 Page 2-7 Issue 9The Awaiting New Command lamp will only illuminate when all phase minimums onall str

Seite 191

T400 Controller Facilities Manual667/EB/20200/000 Page 23-2 Issue 9However, some customers will ask for the push buttons to be wired via the UTCinterf

Seite 192 - VIEW ON SECTION AA

T400 Controller Facilities Manual667/EB/20200/000 Page 24-1 Issue 924. GAS PLINTH24.1 GENERAL DESCRIPTIONA gas plinth can be fitted below the contro

Seite 193 - COVER CLOSED

T400 Controller Facilities Manual667/EB/20200/000 Page 25-1 Issue 925. ANCILLARY PROCESSOR (Integral OTU/LMU/RLM)25.1 GENERAL DESCRIPTIONThe Ancilla

Seite 194

T400 Controller Facilities Manual667/EB/20200/000 Page 25-2 Issue 9On detection of first red lamp failure the RLM response is :-• The T400 system LED

Seite 195

T400 Controller Facilities Manual667/EB/20200/000 Page 25-3 Issue 9Red Lamp Monitor Operation1. The voltage monitor transformer measures the actual vo

Seite 196

T400 Controller Facilities Manual667/EB/20200/000 Page 25-4 Issue 925.1.2 PHYSICAL DESCRIPTION25.1.2(a) Mechanical ConstructionThe PCB is located wi

Seite 197

T400 Controller Facilities Manual667/EB/20200/000 Page 25-5 Issue 925.2 ANCILLARY PROCESSOR CARD INSTALLATION25.2.1 GeneralInstallation and commissi

Seite 198

T400 Controller Facilities Manual667/EB/20200/000 Page 25-6 Issue 925.2.4 CoverThe PCB is fitted with a cover (part number 667/2/25192/000 front, 667

Seite 199

T400 Controller Facilities Manual667/EB/20200/000 Page 25-7 Issue 94. S4 - 600 Ohm/High Impedance SwitchSwitch S4 - Installation(To be performed by qu

Seite 200

T400 Controller Facilities Manual667/EB/20200/000 Page 25-8 Issue 9Figure 25.1 - Ancillary Processor PCB LayoutONS1 - 2/4 Wire SelectorS4 - 600Ω / Hig

Seite 201

T400 Controller Facilities Manual667/EB/20200/000 Page 2-8 Issue 9Each stream will then move immediately to its individual switch off stage subject to

Seite 202

T400 Controller Facilities Manual667/EB/20200/000 Page 25-9 Issue 925.2.6 Connectors and Cables25.2.6(a) Extended System Bus Ribbon CableConnect the

Seite 203

T400 Controller Facilities Manual667/EB/20200/000 Page 25-10 Issue 9Figure 25.2 - LMU Input ConnectorPLB Pin Name Berg Pin PLB Pin Name Berg Pin1 Sens

Seite 204

T400 Controller Facilities Manual667/EB/20200/000 Page 25-11 Issue 9Current TransformersEach controller phase or illuminated indicator that is to be m

Seite 205

T400 Controller Facilities Manual667/EB/20200/000 Page 25-12 Issue 9If the nominal load current (excluding red/ambers) of a particular controlleroutpu

Seite 206 - 20. SPECIAL CONDITIONING

T400 Controller Facilities Manual667/EB/20200/000 Page 25-13 Issue 9current sensors should then be anchored by passing a TYWRAP or equivalent throught

Seite 207

T400 Controller Facilities Manual667/EB/20200/000 Page 25-14 Issue 925.2.7 Effect of Incorrect Switch Settings on the Ancillary Processor PCB (i) S

Seite 208

T400 Controller Facilities Manual667/EB/20200/000 Page 25-15 Issue 925.2.8 Fault Finding at the OutstationSymptom Possible ReasonSystem Fault LED lit

Seite 209

T400 Controller Facilities Manual667/EB/20200/000 Page 25-16 Issue 925.3 RLM GENERAL DESCRIPTION25.3.1 Background InformationThe RLM facility is re

Seite 210

T400 Controller Facilities Manual667/EB/20200/000 Page 25-17 Issue 925.4 ENHANCED RLM DETAILED DESCRIPTIONIn descriptions below, references (C1), (C2

Seite 211

T400 Controller Facilities Manual667/EB/20200/000 Page 25-18 Issue 9For demand dependent phases gaining right-of-way when the RLF1 indication isalread

Seite 212

T400 Controller Facilities Manual667/EB/20200/000 Page 2-9 Issue 9intergreens on the configured stage to stage movements will be held until thesupplem

Seite 213

T400 Controller Facilities Manual667/EB/20200/000 Page 25-19 Issue 925.4.2 Operation On Second Red Lamp FailThe operation of the controller when a se

Seite 214

T400 Controller Facilities Manual667/EB/20200/000 Page 25-20 Issue 925.4.2(a) Configuration OptionsThe effect of a second red lamp fail on the RLM de

Seite 215

T400 Controller Facilities Manual667/EB/20200/000 Page 25-21 Issue 9Only the ‘non-latching’ mode of operation is available on the controller when usin

Seite 216

T400 Controller Facilities Manual667/EB/20200/000 Page 25-22 Issue 925.4.5 Configuration Data(C1) RLM Delayed Phases (PROM item - RLMDFZ)This is an 8

Seite 217

T400 Controller Facilities Manual667/EB/20200/000 Page 25-23 Issue 9(C4) RLF2 Cancel Option (PROM item - RLF2_CANCEL_RLF1)This byte contains one bit f

Seite 218

T400 Controller Facilities Manual667/EB/20200/000 Page 25-24 Issue 9(C7) RLM Phase Delay Times (PROM item - RLMBUV & RAM item - RLMTME)This 16 byt

Seite 219

T400 Controller Facilities Manual667/EB/20200/000 Page 25-25 Issue 9(C12) LMU Moves Array (PROM item - LMUMOV)This is an existing config PROM item whi

Seite 220

T400 Controller Facilities Manual667/EB/20200/000 Page A-1 Issue 9APPENDIX A) SUPPLYING DC POWER FOR VEHICLE DETECTORSTable APPENDIX A) -1 gives the

Seite 221

T400 Controller Facilities Manual667/EB/20200/000 Page A-2 Issue 9Appendix APPENDIX A) .1) Using 24v 2A Internal Supply for DetectorsThere is spare ca

Seite 222

T400 Controller Facilities Manual667/EB/20200/000 Page A-3 Issue 9Appendix APPENDIX A) .2) Using 24v 2A Internal Supply - Cable limitationsTable APPEN

Seite 223

T400 Controller Facilities Manual667/EB/20200/000 Page iii Issue 9ISSUE HISTORYDOCUMENT ISSUE: 8PAGES ISSUE PAGES ISSUE PAGES ISSUEi to xvi 9 10-1 to

Seite 224

T400 Controller Facilities Manual667/EB/20200/000 Page 3-1 Issue 93. PHASES3.1 FACILITIESThere are up to 16 phases (A to P) available for use as any o

Seite 225

T400 Controller Facilities Manual667/EB/20200/000 Page A-4 Issue 9Table APPENDIX A) -4) Number of Detector Boards (SarasotaMTS38Z/36Z/35Z) in External

Seite 226

T400 Controller Facilities Manual667/EB/20200/000 Page A-5 Issue 9Appendix APPENDIX A) .3) Using 27.5v Additional Detector PSUWhere there is insuffici

Seite 227

T400 Controller Facilities Manual667/EB/20200/000 Page A-6 Issue 9Appendix APPENDIX A) .4) Using 27.5v Detector Supply - Cable LimitationsTable APPEND

Seite 228

T400 Controller Facilities Manual667/EB/20200/000 Page A-7 Issue 9Table APPENDIX A) -11) Number of Detector Boards (Sarasota) in ExternalHousing(s) Us

Seite 229

T400 Controller Facilities Manual667/EB/20200/000 Page A-8 Issue 9Appendix APPENDIX A) .5) Cable Distances for SDENOTE: SDE/SA cabling assumes the use

Seite 230

T400 Controller Facilities Manual667/EB/20200/000 Page A-9 Issue 9Table APPENDIX A) -14) Cable Distances for SDE using Sarasota Detectors (2CHANNEL)Ca

Seite 231

T400 Controller Facilities Manual667/EB/20200/000 Page A-10 Issue 9Table APPENDIX A) -15) Maximum Distances for feeder cable when using ‘D’DetectorsLo

Seite 232

T400 Controller Facilities Manual667/EB/20200/000 Page B-1 Issue 9APPENDIX B) 50-0-50 Volt ControllerB.1 50-0-50 volt ControllerNote: This version of

Seite 233

T400 Controller Facilities Manual667/EB/20200/000 Page B-2 Issue 9B.2 Dual Solar Cell (Only Available on 50-0-50 Volt Controller)The solar cell facili

Seite 234

T400 Controller Facilities Manual667/EB/20200/000 Page 3-2 Issue 9The red/amber period is normally 2 seconds and the amber period is normally 3seconds

Seite 235

T400 Controller Facilities Manual667/EB/20200/000 Page 3-3 Issue 93.2.2(b) MCE0141 Audible Indication 2 (High Voltage)The audible signals are driven

Seite 236 - VEHICLES

T400 Controller Facilities Manual667/EB/20200/000 Page 3-4 Issue 9green arrow that appears unconditionally must always be followed by its associatedph

Seite 237

T400 Controller Facilities Manual667/EB/20200/000 Page 3-5 Issue 9The normal functions of a switched sign phase are as follows:3.2.5(a) Secret Regula

Seite 238

T400 Controller Facilities Manual667/EB/20200/000 Page 3-6 Issue 9All phases will normally be set to oppose each other, unless works specifications fo

Seite 239

T400 Controller Facilities Manual667/EB/20200/000 Page 3-7 Issue 93.5.3 Maximum Green (MAX,MBX,MCX,MDX)A maximum green timer is provided for each veh

Seite 240

T400 Controller Facilities Manual667/EB/20200/000 Page 3-8 Issue 9No intergreen period is reduced below its value during phase changes. In the event o

Seite 241

T400 Controller Facilities Manual667/EB/20200/000 Page 3-9 Issue 9(i) Fixed Period during Manual Step-On. (Export only).The timing range is 0 to 255 s

Seite 242

T400 Controller Facilities Manual667/EB/20200/000 Page 3-10 Issue 93.6.1 Minimum Green ThresholdsMinimum Green times have range limits for each phase

Seite 243

T400 Controller Facilities Manual667/EB/20200/000 Page iv Issue 9SUMMARY OF SECTIONS1. INTRODUCTION2. STAGES3. PHASES4. DEMANDS AND EXTENSIONS5. CALL/

Seite 244

T400 Controller Facilities Manual667/EB/20200/000 Page 3-11 Issue 93.7.3 Appearance Type 2The phase will only appear whenever its associated stage ru

Seite 245

T400 Controller Facilities Manual667/EB/20200/000 Page 3-12 Issue 9(ii) The conditional phase is programmed as an Appearance Type 2 andconditioning ti

Seite 246

T400 Controller Facilities Manual667/EB/20200/000 Page 3-13 Issue 9c) be demand dependant3.10 CONDITIONS OF TERMINATION3.10.1 Termination Type 0The

Seite 247

T400 Controller Facilities Manual667/EB/20200/000 Page 4-1 Issue 94. DEMANDS AND EXTENSIONS4.1 GENERAL DESCRIPTIONDemands may be inserted for phases

Seite 248

T400 Controller Facilities Manual667/EB/20200/000 Page 4-2 Issue 94.3.3 Revertive DemandsWhen a vehicle actuated phase terminates with an extension a

Seite 249

T400 Controller Facilities Manual667/EB/20200/000 Page 4-3 Issue 94.4 OPERATION DURING CERTAIN MODES4.4.1 Manual, Fixed Time and Start Up ModeDuring

Seite 250

T400 Controller Facilities Manual667/EB/20200/000 Page 5-1 Issue 95. CALL/CANCEL5.1 GENERALThere are up to 8 call/cancel units (0 to 7) available whic

Seite 251

T400 Controller Facilities Manual667/EB/20200/000 Page 6-1 Issue 96. HIGH SPEED VEHICLE DETECTIONTo provide this facility, an SDE/SA processor PCB an

Seite 252

T400 Controller Facilities Manual667/EB/20200/000 Page 6-2 Issue 96.1.3 SDE Extension InhibitAn SDE extension may be suppressed, but not the associat

Seite 253

T400 Controller Facilities Manual667/EB/20200/000 Page 6-3 Issue 9The condition in (c) is normally disabled for individual phases at the time ofconfig

Seite 254

T400 Controller Facilities Manual667/EB/20200/000 Page v Issue 9CONTENTS1. INTRODUCTION...

Seite 255

T400 Controller Facilities Manual667/EB/20200/000 Page 6-4 Issue 96.8 OTHER LOOP SPACINGSThe SDE/SA facility can be configured to operate with 10 ft.

Seite 256

T400 Controller Facilities Manual667/EB/20200/000 Page 6-5 Issue 9Figure 6.1 - SDE/SA LAYOUTS(c) Speed Assessment151m91m159m79mStopLine12’(3.66m)(a) D

Seite 257

T400 Controller Facilities Manual667/EB/20200/000 Page 7-1 Issue 97. ALL-RED DISPLAYSThere are two methods of achieving an all-red display:- All-re

Seite 258

T400 Controller Facilities Manual667/EB/20200/000 Page 7-2 Issue 97.2 RED EXTENSION DURING INTERGREENThe occupation of an All Red detector loop durin

Seite 259

T400 Controller Facilities Manual667/EB/20200/000 Page 7-3 Issue 9Stage movements for all red units are specified as follows:Unit 7 1 - 2Unit 6 1 - 3U

Seite 260

T400 Controller Facilities Manual667/EB/20200/000 Page 7-4 Issue 9NB Care must be taken when using/testing independent intergreens. The Extend AllRe

Seite 261

T400 Controller Facilities Manual667/EB/20200/000 Page 8-1 Issue 98. PHASE DELAYS8.1 GENERAL DESCRIPTIONIn order to gain more efficient use of phases

Seite 262

T400 Controller Facilities Manual667/EB/20200/000 Page 8-2 Issue 9Figure 8.1 - DELAY PHASE LOSING RIGHT-OF-WAYGREEN...GREENAAMBERAMBERBR/AR/AEF...S

Seite 263

T400 Controller Facilities Manual667/EB/20200/000 Page 8-3 Issue 98.3 PHASES GAINING RIGHT-OF-WAYThe intergreen times from a conflicting phase determ

Seite 264

T400 Controller Facilities Manual667/EB/20200/000 Page 8-4 Issue 98.5 PHASE DELAY HANDSET COMMANDSThere are three handset commands which can be used

Seite 265

T400 Controller Facilities Manual667/EB/20200/000 Page vi Issue 93.6.1 Minimum Green Thresholds ...

Seite 266

T400 Controller Facilities Manual667/EB/20200/000 Page 8-5 Issue 9Figure 8.2 - DELAY PHASE GAINING RIGHT-OF-WAYGREEN...GREENEAMBERAR/AR/AGB...Stage

Seite 267

T400 Controller Facilities Manual667/EB/20200/000 Page 9-1 Issue 99. MODESThe following modes are available: (a) Fixed Time (FT) (b) Vehicle Actua

Seite 268

T400 Controller Facilities Manual667/EB/20200/000 Page 9-2 Issue 9With the mode priorities defined, the controller adopts the highest priority mode fo

Seite 269

T400 Controller Facilities Manual667/EB/20200/000 Page 9-3 Issue 9(b) Amber Leaving/Red Display.Following the blackout an amber leaving signal is show

Seite 270

T400 Controller Facilities Manual667/EB/20200/000 Page 9-4 Issue 9Figure 9.1 - START-UP SEQUENCE BLACK-OUT BLACK-OUT BLACK-OUT BLACK-OUT BLACK-OUTREDR

Seite 271 - 24. GAS PLINTH

T400 Controller Facilities Manual667/EB/20200/000 Page 9-5 Issue 99.2 PART TIME MODEDuring part-time mode, normal traffic control operations are susp

Seite 272

T400 Controller Facilities Manual667/EB/20200/000 Page 9-6 Issue 99.3 URBAN TRAFFIC CONTROL (UTC) MODE(Normally an O.T.U. is required for this facili

Seite 273

T400 Controller Facilities Manual667/EB/20200/000 Page 9-7 Issue 99.3.2 Summary of Control and Reply BitsControl BitsSection Bit designation Title(a)

Seite 274

T400 Controller Facilities Manual667/EB/20200/000 Page 9-8 Issue 99.3.3 Control BitsSee Figure 21.149.3.3(a) Demands - Common (DX) and Stage (D1,D2

Seite 275

T400 Controller Facilities Manual667/EB/20200/000 Page 9-9 Issue 99.3.3(c) Switch Facility (SF1 and SF2)An ‘SF’ bit may be programmed to simulate any

Seite 276

T400 Controller Facilities Manual667/EB/20200/000 Page vii Issue 96.5 SDE/SA PARALLEL STAGE STREAMING FACILITIES ... 6-

Seite 277

T400 Controller Facilities Manual667/EB/20200/000 Page 9-10 Issue 99.3.3(i) Take Over (TO)A ‘TO’ bit may be programmed so that no ‘F’ bits will be ef

Seite 278

T400 Controller Facilities Manual667/EB/20200/000 Page 9-11 Issue 9sets the seconds to 30 (and the sub-seconds counter to 0). The hour is disregarded

Seite 279 - Push down this

T400 Controller Facilities Manual667/EB/20200/000 Page 9-12 Issue 9When ‘G1/G2’ is received at the central office the computer releases controlimmedia

Seite 280

T400 Controller Facilities Manual667/EB/20200/000 Page 9-13 Issue 99.3.4(e) CLF Group Synchronisation Confirm (CS)A ‘CS’ bit may be returned to confi

Seite 281

T400 Controller Facilities Manual667/EB/20200/000 Page 9-14 Issue 9Figure 21.15 indicates where to request the conditions required. In the example sho

Seite 282

T400 Controller Facilities Manual667/EB/20200/000 Page 9-15 Issue 99.3.4(o) Solar Override Confirm (SC)An ‘SC’ reply bit may be returned to indicate

Seite 283

T400 Controller Facilities Manual667/EB/20200/000 Page 9-16 Issue 9A ‘PX’ bit simulates a pedestrian demand.(b) Hold Vehicle Stage (PV)A ‘PV’ bit hold

Seite 284

T400 Controller Facilities Manual667/EB/20200/000 Page 9-17 Issue 9The above conditions may not cause UTC mode to become the current mode due tothe mo

Seite 285

T400 Controller Facilities Manual667/EB/20200/000 Page 9-18 Issue 9am and the real Introduction time of the Plan. The controller then brings the C.L.F

Seite 286

T400 Controller Facilities Manual667/EB/20200/000 Page 9-19 Issue 99.4 PRIORITY AND EMERGENCY VEHICLE MODEPriority and Emergency Vehicle modes provid

Seite 287

T400 Controller Facilities Manual667/EB/20200/000 Page viii Issue 99.5 HURRY CALL MODE ...

Seite 288

T400 Controller Facilities Manual667/EB/20200/000 Page 9-20 Issue 99.4.1(b) Priority ExtensionA continuation of a green signal requested by vehicle(s

Seite 289

T400 Controller Facilities Manual667/EB/20200/000 Page 9-21 Issue 99.4.2 Operational Description9.4.2(a) GeneralUnder no circumstances will the intr

Seite 290

T400 Controller Facilities Manual667/EB/20200/000 Page 9-22 Issue 99.4.2(b) Precedence LevelsFor isolated operation, the normal order of precedence f

Seite 291

T400 Controller Facilities Manual667/EB/20200/000 Page 9-23 Issue 9When the inhibit period is not specified, then irrespective of the normal cyclic st

Seite 292

T400 Controller Facilities Manual667/EB/20200/000 Page 9-24 Issue 9A compensation period will only be introduced on a particular running phase if ther

Seite 293

T400 Controller Facilities Manual667/EB/20200/000 Page 9-25 Issue 9When a priority change from the bus priority level to the emergency vehicle priorit

Seite 294

T400 Controller Facilities Manual667/EB/20200/000 Page 9-26 Issue 99.4.3 Basic FacilitiesReference should be made to Figure 21.16.Both Priority and E

Seite 295

T400 Controller Facilities Manual667/EB/20200/000 Page 9-27 Issue 99.4.3(e) Priority Units Inhibited (Priority Mode Only)When a Priority Phase gains

Seite 296

T400 Controller Facilities Manual667/EB/20200/000 Page 9-28 Issue 9(1) Priority Mode Fault MonitorWhen the input becomes active the Monitor Timer is

Seite 297

T400 Controller Facilities Manual667/EB/20200/000 Page 9-29 Issue 99.4.4 Visual IndicationsA separate indicating light emitting source is normally pr

Seite 298

T400 Controller Facilities Manual667/EB/20200/000 Page ix Issue 911.3 TIMETABLE RESOLUTION ...

Seite 299

T400 Controller Facilities Manual667/EB/20200/000 Page 9-30 Issue 99.4.6 Use of Priority Mode for Control in Light Rail Transit SystemsShown in Figur

Seite 300

T400 Controller Facilities Manual667/EB/20200/000 Page 9-31 Issue 99.4.6(b) Request DelaysThe first delay as indicated allows for the travelling time

Seite 301

T400 Controller Facilities Manual667/EB/20200/000 Page 9-32 Issue 9Figure 9.2 - PRIORITY DEMAND ORDERUSED IN SPECIALCONDITIONING TO PREVENTCERTAIN STA

Seite 302

T400 Controller Facilities Manual667/EB/20200/000 Page 9-33 Issue 99.5 HURRY CALL MODEA hurry call demand gives precedence to a particular stage to e

Seite 303

T400 Controller Facilities Manual667/EB/20200/000 Page 9-34 Issue 9hurry call is valid provided its prevent timer is not active due to a previous hurr

Seite 304 - Stop Line

T400 Controller Facilities Manual667/EB/20200/000 Page 9-35 Issue 9The reasons for a request being rejected may be: (i) The prevent timer being acti

Seite 305

T400 Controller Facilities Manual667/EB/20200/000 Page 9-36 Issue 99.5.3 Control From A Remote PushbuttonIf, on pressing the hurry request button, th

Seite 306

T400 Controller Facilities Manual667/EB/20200/000 Page 9-37 Issue 99.6 SELECTED MANUAL CONTROL MODERefer also to Section 16.MANUAL mode selected on t

Seite 307

T400 Controller Facilities Manual667/EB/20200/000 Page 9-38 Issue 9so. Where parallel stage streaming is employed the indicator will illuminate when t

Seite 308

T400 Controller Facilities Manual667/EB/20200/000 Page 9-39 Issue 99.7 MANUAL STEP-ON MODEA Manual Step-on facility can be provided when a Police Man

Kommentare zu diesen Handbüchern

Keine Kommentare