Power Module PM230 IP55
Features
• Connecting voltage 3AC 380 - 480V +/-10%
• Rated power 0.37 ... 90kW/0.5 ... 125HP (Low Overload)
• Overload capability
Frame Size A – C: 150% for 3 seconds, 110% for 57 seconds, load cycle 300
seconds
Frame Size D – F: 110% for 60 seconds, load cycle 300 seconds
• Degree of protection IP55/UL Type 12 for decentralized mounting
• Environmental temperature 0 ... 40
o
C, with derating up to 60
o
C
• Switching frequency 4kHz, with derating up to 16kHz
• Converter technology with reduced dc link causes reduced line harmonics and
results in reduced cable diameter due to lower line current
• Integrated EMC filter (filter class A) for installations according EN 61800-3
category C2
• Integrated EMC filter (filter class B) for conducted emissions in installations
according EN 61800-3 category C1
• Pluggable motor and power terminals (up to 18,5kW)
• Removable cable connection plate PM can be quickly replaced without
having to disconnect cables
• The fan can be simply replaced at the heat sink