• Connecting voltage 3AC 380 - 480V +/-10%
• Power range 110 ... 400kW / 125 ... 500HP (LO)
based on two frame sizes „GX“ and „HX“
• Overload capability (LO)
135 % for 3 seconds, 100% for 297 seconds, load cycle 300 sec.
110 % for 60 seconds, 100% for 240 seconds, load cycle 300 sec.
• Degree of protection IP20 (standard)
degree of protection IP21, IP23, IP43, IP54 (optional)
• Environmental temperature 0 ... 40
o
C, with derating up to 50
o
C
can be enhanced with optional anti condensing heaters to - 10
o
C
• Two cabinet types available:
Type A: Standard type supporting the complete option spectrum
Type C: Compact version covering a reduced spectrum of options
• IOP provided as default panel solution
• Option variety similar to SINAMICS G150 including Line Harmonic
Filter, without special solutions for marine or chemical industry
• Cabinet delivery includes the complete mounted option package as
a ready for connection and type tested system solution