SINAMICS G120P Cabinet
Features
Connecting voltage 3AC 380 - 480V +/-10%
Power range 110 ... 400kW / 125 ... 500HP (LO)
based on two frame sizes „GX“ and „HX“
Overload capability (LO)
135 % for 3 seconds, 100% for 297 seconds, load cycle 300 sec.
110 % for 60 seconds, 100% for 240 seconds, load cycle 300 sec.
Degree of protection IP20 (standard)
degree of protection IP21, IP23, IP43, IP54 (optional)
Environmental temperature 0 ... 40
o
C, with derating up to 50
o
C
can be enhanced with optional anti condensing heaters to - 10
o
C
Two cabinet types available:
Type A: Standard type supporting the complete option spectrum
Type C: Compact version covering a reduced spectrum of options
IOP provided as default panel solution
Option variety similar to SINAMICS G150 including Line Harmonic
Filter, without special solutions for marine or chemical industry
Cabinet delivery includes the complete mounted option package as
a ready for connection and type tested system solution